STEP 1
Installation Planning
The Dacor Power Packs are designed for installation inside custom hood canopies. Proper installation of the Power Pack is directly related to
the custom canopy material construction. Closely follow the warnings concerning the instatlltion of the Power Pack within a combustible and
non-combustible hood canopy.
A qualified technician must complete the installation of this appliance.
Plan the installation so that all minimum clearances are met or exceeded. Dimensions shown provide minimum clearances, unless otherwise
noted.
CAUTIONS:
1. To reduce the risk of fire and to properly exhaust air the power pack must be exhausted to
outside air. Never exhaust into a wall, an attic or a concealed area in the building. This can
create a potential hazard.
2. Consult a licensed ventilation contractor or qualified technician for proper installation of
exhaust ducting.
3. Locate the cooking area for minimum cross drafts – away from doors and windows, when
possible.
4. Ducts must be of adequate size and duct runs should be as short and straight as possible.
Where turns are necessary, keep turning radius as large and smooth as possible.
5. The ducting must be air tight. Use a minimum of 2 sheet metal screws at every duct joint. Then,
seal the duct joints with a high quality duct tape.
6. Only use ductwork constructed of materials deemed acceptable by state, municipal and local
codes.
NOTE:
1. All dimensional tolerances are + 1/16”, - 0” unless otherwise stated.
Table 1: IVS Specifications
Overall Blower Chassis Width
IVS1/IVSR1 - 22 5/8" (575mm)
IVS2/IVSR2 - 34 1/2" (876mm)
Overall Blower Chassis Depth
12 1/4" (311mm)
Overall Blower Chassis Height
6" (152mm)
Duct Diameter
IVS1/IVSR1 - 8" (203mm)
IVS2/IVSR2 - 2 x 8" (203mm)
Electrical Supply Requirements
120VAC, 60Hz, 15A
Maximum Duct Length
Maximum 60 Equivalent Straight Feet
Total Connected Load
1.4kW (12A)
Blower Rating
IVS1 - 600 CFM IVS2 - 1200 CFM
Approximate Shipping Weight
IVS1/IVSR1 - 24 pounds IVS2/IVSR2 - 32 pounds
SPECIFICATIONS
MEASUREMENTS
WARNINGS:
1. Power packs installed in custom hood canopies, which are contructed of combustible materials,
must be installed with the combustible material structure a minimum of 36 inches above the
appliance burner surface.
2. Power packs installed in custom hood canopies, which are contructed of non-combustible
materials, must be installed with the non-combustible material structure a minimum of 30 inches
above the appliance burner surface.
3. Power packs installed in custom hood canopies, which are contructed utilizing the Dacor IHL
Stainless Steel Hood Liner, must be installed with the non-combustible material structure a
minimum of 30 inches above the appliance burner surface.
4. Follow all instructions regarding minimum safe clearances and installation location. Failure to
do so may reault in a fire or safety hazard.
5. To reduce the risk of fire use only metal duct work.