3   SPECIFICATIONS AND FUNCTIONS 
 
Important 
 
1: The BUSY signal turns ON even when position control of movement amount 0 is 
executed. However, since the ON time is short, the ON status may not be detected in the 
sequence program. 
2: "Positioning complete" of the QD75 refers to the point when the pulse output from QD75 is 
completed.  
Thus, even if the QD75's positioning complete signal turns ON, the system may continue 
operation. 
 
3.3.3 Detail of output signals (CPU module 
 QD75) 
The ON/OFF timing and conditions of the output signals are shown below. 
 
Device No. 
Signal name 
Details 
Y0 PLC 
READY 
OFF: 
PLC READY OFF 
ON: 
PLC READY ON 
(a) This signal notifies the QD75 that the CPU module is normal. 
• It is turned ON/OFF with the sequence program. 
• The PLC READY signal is turned ON during positioning 
control, OPR control, JOG operation, inching operation, and 
manual pulse generator operation, unless the system is in the 
peripheral device test mode. 
(b) When parameters are changed, the PLC READY signal is turned 
OFF depending on the parameter (Refer to CHAPTER 7.). 
(c) The following processes are carried out when the PLC READY 
signal turns from OFF to ON. 
• The parameter setting range is checked. 
• The QD75 READY signal [X0] turns ON. 
(d) The following processes are carried out when the PLC READY 
signal turns from ON to OFF. 
In these cases, the OFF time should be set to 100ms or more. 
• The QD75 READY signal [X0] turns OFF. 
• The operating axis stops. 
• The M code ON signal [X4 to X7] for each axis turns OFF, and 
"0" is stored in "   Md.25   Valid M code". 
(e) When parameters or positioning data (No. 1 to 600) are written 
from the peripheral device or CPU module to the flash ROM, the 
PLC READY signal will turn OFF. 
Y4 
Y5 
Y6 
Y7 
Axis 1 
Axis 2 
Axis 3 
Axis 4 
Axis stop 
OFF: 
Axis stop not 
requested 
ON: 
Axis stop requested
• When the axis stop signal turns ON, the OPR control, positioning 
control, JOG operation, inching operation and manual pulse 
generator operation will stop. 
• By turning the axis stop signal ON during positioning operation, the 
positioning operation will be "stopped". 
• Whether to decelerate or suddenly stop can be selected with 
"  Pr.39   Stop group 3 sudden stop selection". 
• During interpolation control of the positioning operation, if the axis 
stop signal of any axis turns ON, all axes in the interpolation 
control will decelerate and stop. 
Y8 
Y9 
YA 
YB 
YC 
YD 
YE 
YF 
Axis 1 
Axis 1 
Axis 2 
Axis 2 
Axis 3 
Axis 3 
Axis 4 
Axis 4 
Forward run JOG start 
Reverse run JOG start 
Forward run JOG start 
Reverse run JOG start 
Forward run JOG start 
Reverse run JOG start 
Forward run JOG start 
Reverse run JOG start 
OFF: 
JOG not started 
ON: 
JOG started 
• When the JOG start signal is ON, JOG operation will be carried 
out at the "   Cd.17   JOG speed". When the JOG start signal turns 
OFF, the operation will decelerate and stop. 
• When inching movement amount is set, the designated movement 
amount is output for one control cycle and then the operation 
stops. 
Y10 
Y11 
Y12 
Y13 
Axis 1 
Axis 2 
Axis 3 
Axis 4 
Positioning start 
OFF: 
Positioning start not 
requested 
ON: 
Positioning start 
requested 
• OPR operation or positioning operation is started. 
• The positioning start signal is valid at the rising edge, and the 
operation is started. 
• When the positioning start signal turns ON during BUSY, the 
warning "Start during operation" (warning code: 100) will occur. 
Y14 
Y15 
Y16 
Y17 
Axis 1 
Axis 2 
Axis 3 
Axis 4 
Execution prohibition 
flag 
OFF:  
Not during execution 
prohibition 
ON:  
During execution 
prohibition 
• If the execution prohibition flag is ON when the positioning start 
signal turns ON, positioning control does not start until the 
execution prohibition flag turns OFF. (Pulse output not provided) 
Used with the "Pre-reading start function". (Refer to Section 
12.7.7)