FX Series Programmable Controllers
Devices in Detail 4
4-13
4.6.3
Disabling Individual Interrupts
Individual interrupt devices can be temporarily or permanently disabled by driving an
associated special auxiliary relay. The relevant coils are identified in the tables of devices in
chapter 6. However for all PLC types the head address is M8050, this will disable interrupt
I0
.
Driving special auxiliary relays:
Never drive a special auxiliary coil without first checking its use. Not all PLC’s assign the 
same use to the same auxiliary coils.
Disabling high speed counter interrupts
These interrupts can only be disabled as a single group by driving M8059 ON.
Further details about counter interrupts can be found in the following section.
4.6.4
Counter Interrupts
Identification of interrupt pointer number:
Example:
The sequence programmed after the label
(indicated by the I030 pointer) is executed once
t h e  v a l u e   o f   H i g h   S p e e d   C o u n t e r   C 2 5 5
r e a c h e s / e q u a ls   th e   p r e s e t  li m i t   o f   K 1 0 0
identified in the example HSCS.
Additional notes:
Please see the following pages for more details on the HSSC applied instruction.
-
High Speed Counter Set, HSCS FNC 53 - see page 5-55
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)
I  0  
  0
Counter interrupt number 6 points (1 to 6). Counter interrupts can be
entered as the output devices for High Speed Counter Set (HSCS, FNC
53). To disable the Counter Interrupts Special Auxiliary Relay M8059 must
be set ON.
M8000
C255 I030
K100
DHSCS