Справочник Пользователя для Mitsubishi Electronics FX2NC

Скачать
Страница из 382
FX Series Programmable Controllers
Devices in Detail 4
4-15
4.9
Timers
Device Mnemonic: T
Purpose: Timed durations
Alias: Timer(s)
T
Available forms: A driven coil sets internal PLC contacts (NO and NC contacts available).
Various timer resolutions are possible, from 1 to 100 msec, but availability
and quantity vary from PLC to PLC. The following variations are also
available:-
Selectable timer resolutions - see page 4-16
Retentive timers - see page 4-17
Timers used in interrupt and ‘CALL’ subroutines - see page 4-18
Devices numbered in: Decimal, i.e T0 to T9, T10 to T19.
Further uses: None
Example device usage:
Available devices:
\
 Selectable timers taken from the main range of 100 msec timers, see page 4-16.
Timer accuracy:
See page 4-18.
Timer Resolution
 FX
0(S)
FX
0N
FX
FX
(2C)
FX
2N(C)
100 msec
56
(T0 - 55)
63
(T0 - 62)
200
(T0 - 199)
10 msec
\
 24
(T32 - 55)
\
 31
(T32 - 62)
46
(T200 - 245)
1 msec
N/A
1
(T63)
N/A
Retentive 1 msec
N/A
N/A
4
(T246 - 249)
Retentive 100 msec
N/A
N/A
6
(T250 - 255)
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)
X0
T20
K123