Inverter and peripheral devices
1.2.1
Peripheral devices
Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected according to
the capacity. Refer to the following list and prepare appropriate peripheral devices:
200V class
Motor Output 
(kW)
Applicable Inverter Model
Moulded Case Circuit Breaker 
(MCCB) 
or Earth Leakage 
Circuit Breaker (ELB)
(NF or NV type)
Input Side Magnetic Contactor
Power factor improving 
(AC or DC) reactor
Power factor improving 
(AC or DC) reactor
without
with
without
with
0.4
FR-A720-0.4K
5A
5A
S-N10
S-N10
0.75
FR-A720-0.75K
10A
10A
S-N10
S-N10
1.5
FR-A720-1.5K
15A
15A
S-N10
S-N10
2.2
FR-A720-2.2K
20A
15A
S-N10
S-N10
3.7
FR-A720-3.7K
30A
30A
S-N20, S-N21
S-N10
5.5
FR-A720-5.5K
50A
40A
S-N25
S-N20, S-N21
7.5
FR-A720-7.5K
60A
50A
S-N25
S-N25
11
FR-A720-11K
75A
75A
S-N35
S-N35
15
FR-A720-15K
125A
100A
S-N50
S-N50
18.5
FR-A720-18.5K
150A
125A
S-N65
S-N50
22
FR-A720-22K
175A
150A
S-N80
S-N65
30
FR-A720-30K
225A
175A
S-N95
S-N80
37
FR-A720-37K
250A
225A
S-N150
S-N125
45
FR-A720-45K
300A
300A
S-N180
S-N150
55
FR-A720-55K
400A
350A
S-N220
S-N180
75 FR-A720-75K
400A
S-N300
90 FR-A720-90K
400A
S-N300
*1
Motor Output (kW) in the above table indicates values when using the Mitsubishi 4-pole standard motor with power supply voltage of 200VAC
50Hz.
*2
Select the MCCB according to the power supply capacity. Install one MCCB per inverter.
For installation in the United States or Canada, select a fuse in accordance with UL, cUL, the National
Electrical Code and any applicable local codes, or use UL 489 Molded Case Circuit Breaker (MCCB).
 (Refer to 
 Instruction Manual (basics).)
*3
Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during motor driving, select an MC regarding the inverter input side current as JEM1038-AC-3 class rated
current. When using an MC on the inverter output side for commercial-power supply operation switching using a general purpose motor, select an
MC regarding the motor rated current as JEM1038-AC-3 class rated current.
CAUTION
⋅ When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model and cable and reactor according to the motor output.
⋅ When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
MCCB
INV
MCCB
INV
IM
IM