Inverter and peripheral devices
1
400V class
Motor Output 
(kW)
Applicable Inverter Model
Moulded Case Circuit Breaker 
(MCCB) 
*2 
or Earth Leakage 
Circuit Breaker (ELB)
(NF or NV type)
Input Side Magnetic Contactor
Power factor improving 
(AC or DC) reactor
Power factor improving 
(AC or DC) reactor
without
with
without
with
0.4
FR-A740-0.4K
5A
5A
S-N10
S-N10
0.75
FR-A740-0.75K
5A
5A
S-N10
S-N10
1.5
FR-A740-1.5K
10A
10A
S-N10
S-N10
2.2
FR-A740-2.2K
10A
10A
S-N10
S-N10
3.7
FR-A740-3.7K
20A
15A
S-N10
S-N10
5.5
FR-A740-5.5K
30A
20A
S-N20, S-N21
S-N11, S-N12
7.5
FR-A740-7.5K
30A
30A
S-N20, S-N21
S-N20, S-N21
11
FR-A740-11K
50A
40A
S-N20, S-N21
S-N20, S-N21
15
FR-A740-15K
60A
50A
S-N25
S-N20, S-N21
18.5
FR-A740-18.5K
75A
60A
S-N25
S-N25
22
FR-A740-22K
100A
75A
S-N35
S-N25
30
FR-A740-30K
125A
100A
S-N50
S-N50
37
FR-A740-37K
150A
125A
S-N65
S-N50
45
FR-A740-45K
175A
150A
S-N80
S-N65
55
FR-A740-55K
200A
175A
S-N80
S-N80
75
FR-A740-75K
225A
S-N95
90
FR-A740-90K
225A
S-N150
110
FR-A740-110K
225A
S-N180
132
FR-A740-132K
400A
S-N220
160
FR-A740-160K
400A
S-N300
185
FR-A740-185K
400A
S-N300
220
FR-A740-220K
500A
S-N400
250
FR-A740-250K
600A
S-N600
280
FR-A740-280K
600A
S-N600
315
FR-A740-315K
700A
S-N600
355
FR-A740-355K
800A
S-N600
400
FR-A740-400K
900A
S-N800
450
FR-A740-450K
1000A
1000A
Rated product
500
FR-A740-500K
1200A
1000A
Rated product
*1
Motor Output (kW) in the above table indicates values when using the Mitsubishi 4-pole standard motor with power supply voltage of 400VAC
50Hz.
*2
Select the MCCB according to the power supply capacity. Install one MCCB per inverter.
For installation in the United States or Canada, select a fuse in accordance with UL, cUL, the National
Electrical Code and any applicable local codes, or use UL 489 Molded Case Circuit Breaker (MCCB).
 (Refer to 
 Instruction Manual (basics).)
*3
Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during motor driving, select an MC regarding the inverter input side current as JEM1038-AC-3 class rated
current. When using an MC on the inverter output side for commercial-power supply operation switching using a general purpose motor, select an
MC regarding the motor rated current as JEM1038-AC-3 class rated current.
CAUTION
⋅ When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model, and select cable and reactor according to the motor output.
⋅ When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
MCCB
INV
MCCB
INV
IM
IM