Wiring
2.1 Wiring
2.1.1
Terminal connection diagram
CAUTION
· To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables. Also separate the main circuit wire
of the input side and the output side. 
· After wiring, wire offcuts must not be left in the inverter.Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
· Set the voltage/current input switch correctly. Different setting may cause a fault, failure or malfunction.
R/L1
S/L2
T/L3
R1/L11
S1/L21
PC
10E(+10V)
10(+5V)
2
(Analog common)
2
3
1
1
4
Jumper
C1
B1
A1
U
V
W
P1
0 to 
±10VDC
*1
0 to 5VDC
0 to 10VDC
MC
Main circuit
Control circuit
C2
B2
A2
IM
0 to 20mADC
AU
PTC
TXD+
TXD-
RXD+
RXD-
SG
GND
SINK
SOURCE
*4
*3
*5
STF
STR
STOP
RH
RM
RL
JOG
RT
MRS
RES
AU
CS
SD
RUN
SU
IPF
OL
FU
SE
(+)
(-)
5
ON
OFF
VCC
(+)
(-)
5V
*2
Earth (Ground) 
PX
PR
N/-
P/+
*8
*3.JOG terminal can be used 
as pulse train input terminal.
Use Pr. 291 to select 
JOG/pulse.
Main circuit terminal
Control circuit terminal
Three-phase AC 
power supply
MCCB
Jumper
Earth
(Ground) 
EMC filter
ON/OFF
connecter
Earth
(Ground)
selectable
selectable
0 to 
±5VDC
*5
4 to 20mADC
0 to 5VDC
0 to 10VDC
selectable
*5
Option connector 1
Option connector 2
Option connector 3
Connector 
for plug-in option 
connection
Frequency setting signal (Analog)
Frequency setting
 potentiometer
1/2W1k
Ω
*6
Control input signals (No voltage input allowed)
Forward
rotation
start
Reverse
rotation
start
Start self-
holding selection
Terminal functions vary with 
the input terminal 
assignment (Pr. 178 to Pr. 189)
Middle
speed
High speed
Low speed
Multi-speed 
selection
Jog operation
Second function selection
Output stop
Reset
Terminal 4 input selection
(Current input selection)
Selection of automatic restart 
after instantaneous 
power failure
USB
connector
PU
connector
Terminating
 resistor
Data reception
Data transmission
RS-485 terminals
Open collector output common
Sink
/source common
Frequency detection
Running
Up to frequency
Instantaneous 
power failure
Overload
Terminal functions 
vary with the output 
terminal assignment 
(Pr. 190 to Pr. 194)
Open collector output
(Permissible load 
current 100mA)
Relay output 2
Relay output 1
(Fault output)
Terminal functions 
vary with the output 
terminal assignment 
(Pr. 195, Pr. 196)
Relay output
Motor
*4.  AU terminal can be 
used as PTC input 
terminal.
*2.  To supply power to the 
control circuit separately, 
remove the jumper across 
R1/L11 and S1/L21.
*10. It is not necessary 
when calibrating the 
indicator from the 
operation panel.
*6.  It is recommended to use 2W1k
Ω 
when the frequency setting signal 
is changed frequently. 
Jumper
(Initial value)
(Initial value)
(Initial value)
ON
4 2
OFF
Voltage/current 
input switch
*5
Auxiliary 
input
Terminal 
4 input
(Current 
input)
Brake unit
(Option)
CN8
*7
Jumper
*5.  Terminal input specifications 
can be changed by analog 
input specifications 
switchover (Pr. 73, Pr. 267). 
Set the voltage/current input 
switch in the OFF position to 
select voltage input (0 to 5V/0 
to10V) and ON to select 
current input (4 to 20mA).
R
R
        *1. DC reactor (FR-HEL)
Be sure to connect the DC reactor 
supplied with the 75K or higher.
When a DC reactor is connected to 
the 55K or lower, remove the jumper 
across P1 and P/+.
*7.  A CN8 connector (for MT-BU5) is provided 
with the 75K or higher.
Sink logic
*8. Brake resistor (FR-ABR)
Remove the jumper across terminal PR-PX 
when connecting a brake resistor.
(0.4K to 7.5K)
Terminal PR is provided for the 0.4K to 22K.
Install a thermal relay to prevent an overheat 
and burnout of the brake resistor.
*9
*9.The FR-A720-0.4K and 0.75K 
are not provided with the EMC
filter ON/OFF connector. (Always on)
FM
SD
+
-
AM
5
*11
*11. FM terminal can 
be used for pulse
train output of open 
collector output 
using Pr.291.
(+)
(-)
(0 to 10VDC)
Analog signal output
Moving-coil type
1mA full-scale
(Frequency meter, etc.)
Indicator
Calibration 
resistor *10
24VDC power supply
(Common for external power supply transistor)
Contact input common
24V
Inrush current 
limit circuit
(Refer to page 286)
(Refer to page 231)
(Refer to page 239)
(Refer to page 239)
(Refer to page 45)