Main circuit terminal specifications
2.2 Main circuit terminal specifications
2.2.1
Specification of main circuit terminal
2.2.2
Terminal arrangement of the main circuit terminal, power supply and the motor 
wiring.
Terminal 
Symbol
Terminal Name
Description
Refer 
to 
page
R/L1, 
S/L2, 
T/L3
AC power input
Connect to the commercial power supply.
Keep these terminals open when using the high power factor converter (FR-
HC and MT-HC) or power regeneration common converter (FR-CV).
U, V, W
Inverter output
Connect a three-phase squirrel-cage motor.
R1/L11, 
S1/L21
Power supply for 
control circuit
Connected to the AC power supply terminals R/L1 and S/L2. To retain the 
fault display and fault output or when using the high power factor converter 
(FR-HC and MT-HC) or power regeneration common converter (FR-CV), 
remove the jumpers from terminals R/L1-R1/L11 and S/L2-S1/L21 and apply 
external power to these terminals.
The power capacity necessary when separate power is supplied from R1/
L11 and S1/L21 differs according to the inverter capacity.
P/+, PR
Brake resistor 
connection
(22K or lower)
Remove the jumper from terminals PR-PX (7.5K or lower) and connect an 
optional brake resistor (FR-ABR) across terminals P/+-PR.
For the 22K or lower, connecting the resistor further provides regenerative 
braking power.
P/+, N/-
Brake unit 
connection
Connect the brake unit (FR-BU2, FR-BU, BU and MT-BU5), power 
regeneration common converter (FR-CV), power regeneration converter 
(MT-RC), high power factor converter (FR-HC and MT-HC) or DC power 
supply (under the DC feeding mode).
P/+, P1
DC reactor 
connection
For the 55K or lower, remove the jumper across terminals P/+ - P1 and 
connect the DC reactor. (As a DC reactor is supplied with the 75K or higher 
as standard, be sure to connect the DC reactor.)
Keep the jumper across P/+ and P1 attached when a DC reactor is not 
connected.
PR, PX
Built-in brake circuit 
connection
When the jumper is connected across terminals PX-PR (initial status), the 
built-in brake circuit is valid. (Provided for the 7.5K or lower.)
Earth (Ground)
For earthing (grounding) the inverter chassis. Must be earthed (grounded).
CAUTION
· When connecting a dedicated brake resistor (FR-ABR) and brake unit (FR-BU2, FR-BU, BU) remove jumpers across terminals
PR-PX  (7.5K or lower). For details, refer to page 40.
FR-A720-0.4K, 0.75K
FR-A720-1.5K to 3.7K
FR-A740-0.4K to 3.7K
11K or lower
15K
18.5K or higher
200V class
60VA
80VA
80VA
400V class
60VA
60VA
80VA
R/L1 S/L2 T/L3
N/-
P/+
PR
PX
R1/L11 S1/L21
Charge lamp
Jumper
Jumper
Motor
Power supply
IM
R/L1 S/L2 T/L3
N/-
P/+
PR
PX
R1/L11 S1/L21
IM
Charge lamp
Jumper
Jumper
Motor
Power
supply