Monitor display and monitor output signal
4
4.16 Monitor display and monitor output signal
4.16.1 Speed display and speed setting (Pr. 37, Pr. 144, Pr. 505, Pr. 811)
* The maximum value of the setting range differs according to the Pr. 1 Maximum frequency and Pr. 505 Speed setting reference settings
and it can be calculated from the following formula.
Maximum setting value of Pr. 37 <
Note that the maximum setting value of Pr. 37 is 9998 if the result of the above formula exceeds 9998.
Purpose
Parameter that must be Set
Refer to Page
Display motor speed
Set speed
Speed display and speed 
setting
Pr. 37, Pr. 144, Pr. 505, Pr. 811
Change PU monitor display data
DU/PU main display data 
selection
Cumulative monitor clear
Pr. 52,  Pr. 170,  Pr. 171, Pr. 268, Pr. 891
Change of the monitor output 
from terminal FM and AM
Terminal FM, AM function 
selection
Pr. 54, Pr. 158, Pr. 291, Pr. 866, Pr. 867
Set the reference of the monitor 
output from terminal FM and AM
Setting of reference of 
terminal FM and AM
Pr. 55, Pr. 56, Pr. 291, Pr. 866, Pr. 867
Adjust terminal FM, AM outputs
Terminal FM, AM 
calibration
Pr. 900, Pr. 901
You can change the PU (FR-DU07/FR-PU04/FR-PU07) monitor display or frequency setting to motor speed or
machine speed.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
37
Speed display
0
0
Frequency display, setting
1 to 9998*
Set the machine speed at Pr. 505.
144
Speed setting switchover
4
0, 2, 4, 6, 8, 
10, 102, 104, 
106, 108, 110
Set the number of motor poles when displaying the motor speed.
505
Speed setting reference
60Hz
1 to 120Hz Set the reference speed for Pr. 37.
811
Set resolution switchover
0
Speed setting and running 
speed monitor increments from 
the PU, RS-485 communication 
or communication option.
Torque limit setting increments
Pr. 22, Pr. 812 to Pr. 817
0
1r/min
0.1%
1
0.1r/min
10
1r/min
0.01%
11
0.1r/min
65535 
×
 Pr. 505
Setting value of Pr. 1 (Hz)