4.16.2 DU/PU, FM, AM terminal monitor display selection (Pr. 52, Pr. 54, Pr. 158, Pr. 170, 
Pr. 171, Pr. 268, Pr. 563, Pr. 564, Pr. 891)
(1) Monitor description list (Pr. 52)
⋅ Set the monitor to be displayed on the operation panel (FR-DU07) and parameter unit (FR-PU04/FR-PU07) in Pr.
52 DU/PU main display data selection.
⋅ Set the monitor to be output to the terminal FM (pulse train output) in Pr. 54 FM terminal function selection.
⋅ Set the monitor to be output to the terminal AM (analog voltage output (0 to 10VDC voltage output)) in Pr. 158 AM
terminal function selection.
⋅ Refer to the following table and set the monitor to be displayed. (The signals marked × cannot be selected for
monitoring)
The monitor to be displayed on the main screen of the operation panel (FR-DU07)/parameter unit (FR-PU04/FR-
PU07) can be selected.
In addition, signals to be output from the terminal FM (pulse train output) and AM (analog voltage output) can be
selected.
Parameter 
Number
Name
Initial Value
Setting Range
Description
52*
DU/PU main display data 
selection
0
(output 
frequency)
0, 5 to 14, 17 to  
20, 22 to 25, 
32 to 35, 39, 46, 
50 to 57, 100
Select the monitor to be displayed on the 
operation panel and parameter unit.
Refer to the following table for monitor description.
54*
FM terminal function 
selection
1
(output 
frequency)
1 to 3, 5 to 14, 
17, 18, 21, 24, 32 
to 34, 46, 50, 52, 
53
Select the monitor output to terminal FM.
158*
AM terminal function 
selection
Select the monitor output to terminal AM.
170
Watt-hour meter clear
9999
0
Set "0" to clear the watt-hour meter monitor.
10
Sets the maximum value for the monitoring from 
communication to 9999kWh. 
9999
Sets the maximum value for the monitoring from 
communication to 65535kWh.
171
Operation hour meter clear
9999
0, 9999
Set "0" to clear the operation time monitor.
Setting "9999" has no effect.
268*
Monitor decimal digits 
selection
9999
0
Displayed as integral value
1
Displayed in 0.1 increments
9999
No function
563
Energization time 
carrying-over times
0
0 to 65535
(reading only)
The numbers of cumulative energization time 
monitor exceeded 65535h is displayed. Reading 
only
564
Operating time carrying-
over times
0
0 to 65535
(reading only)
The numbers of operation time monitor 
exceeded 65535h is displayed. Reading only
891
Cumulative power monitor 
digit shifted times
9999
0 to 4
Set the number of times to shift the cumulative 
power monitor digit.
Clamp the monitoring value at maximum.
9999
No shift
Clear the monitor value when it exceeds the 
maximum value.
* The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection.
............. Specifications differ according to the date assembled. Refer to page 484  to check the SERIAL number.
Types of Monitor
Increments
Pr. 52 Setting
Pr. 54 (FM) 
Pr. 158 (AM)  
Setting
Full-scale 
Value of the 
Terminal FM 
and AM
Description
DU LED
PU main
monitor
Output frequency
0.01Hz
0/100
1
Pr. 55
Display the inverter output frequency.
Output current 
0.01A/0.1A 
0/100
2
Pr. 56
Display the inverter output current effective 
value.
Output voltage
0.1V
0/100
3
200V class:
400V
400V class:
800V
Display the inverter output voltage.
Fault display
0/100
×
Display 8 past alarms individually.