309
setting restriction
4
(2) User group function (Pr. 160, Pr. 172 to Pr. 174)
⋅ The user group function is designed to display only the parameters necessary for setting.
⋅ From among all parameters, a maximum of 16 parameters can be registered to a user group. When Pr. 160 is set to
"1", only the parameters registered to the user group can be accessed. (Reading of parameters other than the user
group registration is disabled.)
⋅ To register a parameter to the user group, set its parameter number to Pr. 173.
⋅ To delete a parameter from the user group, set its parameter number to Pr. 174. To batch-delete the registered
parameters, set Pr. 172 to "9999".
(3) Registration of parameter to user group (Pr. 173)
(4) Deletion of parameter from user group (Pr. 174)
When registering Pr. 3  to user group
When deleting Pr. 3  from user group
REMARKS
⋅ Pr. 77, Pr. 160 and Pr. 991 can always be read, independently of the user group setting.
⋅ Pr. 77, Pr. 160 and Pr. 172 to Pr. 174  cannot be registered to the user group.
⋅ When Pr. 174 is read, "9999" is always displayed. Although "9999" can be written, no function is available.
⋅ When any value other than "9999" is set to Pr. 172, no function is available.
♦ Parameters referred to 
Pr. 550  NET mode operation command source selection  
 
Refer to page 322
Pr. 551 PU mode operation command source selection  
 
Refer to page 322
Indication
Operation
Parameter setting mode
Pr. 173 User group 
registration is displayed.
When Pr. 173 is read, 
"9999" is displayed.
Select the parameter 
number to be registered.
Flicker
 
··· 
Registration of 
Pr. 3 to user group 
                completed!!
1.
Confirm the operation display and operation 
     mode display.
      The inverter must be at a stop.
      The inverter must be in the PU operation mode.
       (Press          in the External operation mode.)
2.
Press          to choose the parameter setting
     mode.
3.
Turn           until               appears.
5.
Turn           until Pr. 3 appears.
6.
Press          to set.
     "               " and "    " are displayed alternately.
To continue parameter registration, repeat 
steps 3 to 6.
4.
Press          to display. "              "
Operation
1.
Confirm the operation display and operation 
    mode display.
     The inverter must be at a stop.
     The inverter must be in the PU operation mode.
      (Press          in the External operation mode.)
2.
Press          to choose the parameter setting
    mode.
3.
Turn           until               appears.
5.
Turn           until Pr. 3 appears.
6.
Press          to clear.
    "               " and "    " are displayed alternately.
To continue parameter registration, repeat 
steps 3 to 6.
4.
Press          to display. "              "
Indication
Parameter setting mode
Pr. 174 User group 
clear is displayed.
When Pr. 174 is read, 
"9999" is displayed.
Select the parameter 
number to be deleted.
Flicker
 
··· 
Deletion of 
Pr. 3 from user group
                completed!!