310
Misoperation prevention and parameter 
4.22.5 Password function (Pr. 296, Pr. 297)
(1) Parameter reading/writing restriction level (Pr. 296)
Level of reading/writing restriction by PU/NET operation mode operation command can be selected by Pr. 296.
Registering a 4-digit password can restrict parameter reading/writing.
Parameter
Number
Name
Initial Value
Setting Range
Description
296 
*2
Password lock level
9999
0 to 6, 99, 100 to 
106, 199
Select restriction level of parameter reading/
writing when a password is registered.
9999
No password lock
297 
*2
Password lock/unlock
9999
1000 to 9998
Register a 4-digit password
(0 to 5)
 
*1
Displays password unlock error count. 
(Reading only) (Valid when Pr. 296 = "100" 
to "106", "199")
9999
 
*1
No password lock
The above parameters can be set when Pr. 160 User group read selection = "0".
When Pr. 296 
≠ "9999" (with password lock), note that Pr. 297 is always available for setting regardless of Pr. 160 setting.
*1
Only Pr.297 can be set anytime as Pr.297 = "0 or 9999." However, the setting is invalid (the displayed value does not change).
*2
This parameter allows its setting to be changed during operation in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter
write selection
.
...............Specifications differ according to the date assembled. Refer to page 484  to check the SERIAL number.
Pr. 296 Setting
PU Operation Mode Operation 
Command
 
NET Operation Mode Operation Command
RS-485 Terminals
Communication Option
Read
Write
Read
Write
Read
Write
9999
0, 100
×
×
×
×
×
×
1, 101
×
×
×
2, 102
×
3, 103
×
×
4, 104
×
×
×
×
×
5, 105
×
×
6, 106
×
×
×
99, 199
Only parameters registered in the user group can be read/written.
 *5
(For the parameters not registered in the user group, same restriction level as "4, 104" applies.)
: enabled, 
×: restricted
*1
If the parameter reading is restricted by the Pr. 160 setting, those parameters are unavailable for reading even when " " is indicated.
*2
If the parameter writing is restricted by the Pr. 77 setting, those parameters are unavailable for writing even when " " is indicated.
*3
This restricts parameter access from the command source that can write a parameter under the PU operation mode (initially the operation panel
(FR-DU07) or the parameter unit). (For how to select the PU mode command source, refer to page 322.)
*4
This restricts parameter access from the command source that can write a parameter under the Network operation mode (initially the RS-485
terminals or a communication option). (For how to select the NET mode command source, refer to page 322.)
*5
Read/write is enabled only in the simple mode parameters registered in the user group when Pr.160 User group read selection = "9999".
Pr.296 and Pr.297 are always read/write enabled whether registered to a user group or not.
*6
If a communication option is installed, option fault (E.OPT) occurs, and inverter trips. (Refer to page 412.)