321
Selection of operation mode and operation location
4
4.23.2 Operation mode at power ON (Pr. 79, Pr. 340)
(1) Specify operation mode at power ON (Pr. 340)
⋅ Depending on the Pr. 79 and Pr. 340 settings, the operation mode at power ON (reset) changes as described below.
When power is switched ON or when power comes back ON after instantaneous power failure, the inverter can
be started up in Network operation mode.
After the inverter has started up in the Network operation mode, parameter write and operation can be performed
from a program.
Set this mode for communication operation using the RS-485 terminals or communication option.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
79 
Operation mode selection
0
0 to 4, 6, 7 Select the operation mode. (Refer to page 315.)
34
Communication startup 
mode selection
0
0
As set in Pr. 79.
1, 2
Started in Network operation mode.
When the setting is "2", it will resume the pre-instantaneous power 
failure operation mode after an instantaneous power failure occurs.
10, 12
Started in Network operation mode. Operation mode can be 
changed between the PU operation mode and Network operation 
mode from the operation panel. When the setting is "12", it will 
resume the pre-instantaneous power failure operation mode after 
an instantaneous power failure occurs.
The above parameters can be changed during a stop in any operation mode.
*1
This parameter allows its setting to be changed in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter write selection.
*2
This parameter allows its setting to be changed in any operation mode even if "0 (initial value)" is set in Pr. 77 Parameter write selection.
*3
The parameters can be set whenever the communication option is connected. (Refer to page 308.).
Pr. 340
Setting
Pr. 79
Setting
Operation Mode at Power ON, Power 
Restoration, Reset
Operation Mode Switching
0
(initial 
value)
0
(initial 
value)
External operation mode
Switching among the external, PU, and NET operation mode is 
enabled 
*2
1
PU operation mode
Fixed to PU operation mode
2
External operation mode
Switching between the external and Net operation mode is 
enabled
Switching to PU operation mode is disabled
3, 4
External/PU combined operation mode
Operation mode switching is disabled
6
External operation mode
Switching among the external, PU, and NET operation mode is 
enabled while running
7
External operation mode when X12 (MRS) signal 
ON
Switching among the external, PU, and NET operation mode is 
enabled 
*2
External operation mode when X12 (MRS) signal 
OFF
Fixed to External operation mode (forcibly switched to External 
operation mode.)
1, 2 
*1
0
NET operation mode
Same as when Pr. 340 = "0"
1
PU operation mode
2
NET operation mode
3, 4
External/PU combined operation mode
6
NET operation mode
7
NET operation mode when X12 (MRS) signal ON
External operation mode when X12 (MRS) signal 
OFF
10, 12
 
 
*1
0
NET operation mode
Switching between the PU and NET operation mode is 
enabled 
*3
1
PU operation mode
Same as when Pr. 340 = "0"
2
NET operation mode
Fixed to NET operation mode
3, 4
External/PU combined operation mode
Same as when Pr. 340 = "0"
6
NET operation mode
Switching among the external, PU, and NET operation mode is 
enabled while running 
*3
7
External operation mode
Same as when Pr. 340 = "0"
*1
The Pr. 340  setting "2" or "12" is mainly used for communication operation using the inverter RS-485 terminals. When a value other than "9999"
(selection of automatic restart after instantaneous power failure) is set in Pr. 57 Restart coasting time, the inverter will resume the same operation
state which was in before after power has been restored from an instantaneous power failure.
When Pr. 340 = "1, 10", a start command turns OFF if power failure has occurred and then restored during a start command is ON.
*2
The operation mode cannot be switched directly between the PU operation mode and Network operation mode.
*3
Operation mode can be changed between the PU operation mode and Network operation mode with 
 key of the operation panel (FR-
DU07) and X65 signal.
♦ Parameters referred to 
Pr. 57 Restart coasting time  
 Refer to page 266.
Pr. 79 Operation mode selection  
 Refer to page 313.