Справочник Пользователя для Mitsubishi Electronics FR-A700

Скачать
Страница из 523
323
Selection of operation mode and operation location
4
(2) Select the command source of the PU operation mode (Pr. 551)
⋅ Any of the PU connector, RS-485 terminals, or USB connector can be specified as the command source in the PU
operation mode.
⋅ Set Pr.551="1" to use the RS-485 terminals to write parameters or send start and frequency commands in the PU
operation mode. Set Pr.551="3 or 9999" to use the USB connector to do those in the PU operation mode. 
*1
The Modbus-RTU protocol cannot be used in the PU operation mode. When using the Modbus-RTU protocol, set Pr. 551 to "2".
*2
When the communication option is not fitted, the operation mode cannot be switched to Network operation mode.
*3
When Pr. 551 = "9999", the priorities of the PU command source is USB connector > PU connector.
CAUTION
⋅ The PU operation mode has a higher priority when Pr. 550 = "1" (NET mode RS-485 terminals) and Pr. 551 = "1" (PU mode RS-485
terminals). When the communication option is not fitted, therefore, the operation mode cannot be switched to Network operation
mode.
⋅ Changed setting value is valid when powering ON or resetting the inverter.
Pr. 550
Setting
Pr. 551
Setting
Command Source
Remarks
PU connector
USB connector
RS-485 terminals Communication option
0
1
×
×
PU operation mode
 
*1
NET operation mode 
*2
2
PU operation mode
×
×
NET operation mode 
*2
3
×
PU operation mode
×
NET operation mode 
*2
9999
 
(initial 
value)
PU operation mode 
*3
PU operation mode 
*3
×
NET operation mode 
*2
1
1
×
×
PU operation mode
 
*1
×
Switching to NET 
operation mode disabled
2
PU operation mode
×
NET operation mode
×
3
×
PU operation mode
 
NET operation mode
×
9999 
(initial 
value)
PU operation mode 
*3
PU operation mode 
*3
NET operation mode
×
9999
(initial 
value)
1
×
×
PU operation mode 
*1
NET operation mode 
*2
2
PU operation mode
×
×
NET operation mode 
*2
Communication option 
fitted
NET operation mode
×
Communication option 
not fitted
3
×
PU operation mode
 
×
NET operation mode 
*2
Communication option 
fitted
NET operation mode
×
Communication option 
not fitted
9999
 
(initial 
value)
PU operation mode 
*3
PU operation mode 
*3
×
NET operation mode 
*2
Communication option 
fitted
NET operation mode
×
Communication option 
not fitted