Справочник Пользователя для Mitsubishi Electronics FR-A700

Скачать
Страница из 523
443
Inverter rating
400V class
Model FR-A740-……K
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
Applicable motor capacity (kW) 
*1
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
Ou
tp
u
t
Rated capacity (kVA) 
*2
1.1
1.9
3
4.6
6.9
9.1
13
17.5
23.6
29
32.8
43.4
54
65
84
Rated current (A) 
1.5
2.5
4
6
9
12
17
23
31
38
44
57
71
86
110
Overload current rating 
*5
150% 60s, 200% 3s (inverse-time characteristics) surrounding air temperature 50°C
Rated voltage
 *6
Three-phase 380 to 480V
Regenerative 
braking torque
Maximum value/
permissible duty
100% torque/2%ED
*6
20% torque/continuous
 
*6
20% torque/continuous
Pow
e
r supp
ly Rated input
AC voltage/frequency
Three-phase 380 to 480V 50Hz/60Hz
Permissible AC voltage fluctuation
323 to 528V 50Hz/60Hz
Permissible frequency fluctuation
±
5%
Power supply capacity (kVA) 
*7
1.5
2.5
4.5
5.5
9
12
17
20
28
34
41
52
66
80
100
Protective structure 
*9
Enclosed type (IP20)
 
*9
Open type (IP00)
Cooling system
Self-cooling
Forced air cooling
Approx. mass (kg)
3.8
3.8
3.8
3.8
3.8
7.1
7.1
7.5
7.5
13
13
23
35
35
37
Model FR-A740-……K
75
90
110
132
160
185
220
250
280
315
355
400
450
500
Applicable motor capacity (kW) 
*1
75
90
110
132
160
185
220
250
280
315
355
400
450
500
Ou
tp
u
t
Rated capacity (kVA) 
*2
110
137
165
198
248
275
329
367
417
465
521
587
660
733
Rated current (A)
*3
144
(122)
180
(153)
216
(184)
260
(221)
325
(276)
361
(307)
432
(367)
481
(409)
547
(465)
610
(519)
683
(581)
770
(655)
866
(736)
962
(818)
Overload current rating 
*4
150% 60s, 200% 3s (inverse-time characteristics) surrounding air temperature 50°C
Rated voltage
*5
Three-phase 380 to 480V
Regenerative 
braking torque
Maximum value/
permissible duty
10% torque/continuous
Power
 s
uppl
y Rated input
AC voltage/frequency
Three-phase 380 to 480V 50Hz/60Hz
Permissible AC voltage fluctuation
323 to 528V 50Hz/60H
Permissible frequency fluctuation
±
5%
Power supply capacity (kVA) 
*7
110
137
165
198
248
275
329
367
417
465
521
587
660
733
Protective structure (JEM 1030) 
*9
Open type (IP00)
Cooling system
Forced air cooling
Approx. mass (kg)
50
57
72
72
110
110
175
175
175
260
260
370
370
370
*1. The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
*2. The rated output capacity indicated assumes that the output voltage is 440V.
*3. When operating the inverter of 75K or higher with a value larger than 2kHz set in Pr. 72 PWM frequency selection, the rated output current is the value in
parentheses.
*4. The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for
the inverter and motor to return to or below the temperatures under 100% load.
*5. The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
the pulse voltage value of the inverter output side voltage remains unchanged at about 
 that of the power supply.
*6. With the dedicated external brake resistor FR-ABR-H (option), the 0.4K to 7.5K and 11K to 22K will achieve the performance of 100% torque/10%ED and
100% torque/6%ED respectively.
*7. The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
*8. When the hook of the inverter front cover is cut off for installation of the plug-in option, protective structure of the inverter changes to an open type (IP00).
*9. FR-DU07:IP40 (except for the PU connector)
2