Common specifications
7.3 Common specifications
Con
trol specifications
Control method
Soft-PWM control/high carrier frequency PWM control (V/F control, Advanced magnetic flux vector control and Real sensorless 
vector control are available) / vector control 
Output frequency range
0.2 to 400Hz (The maximum frequency is 120Hz under Real sensorless vector control and vector control
.)
Frequency 
setting 
resolution
Analog input
0.015Hz/60Hz (terminal 2, 4: 0 to 10V/12bit)
0.03Hz/60Hz (terminal 2, 4: 0 to 5V/11bit, 0 to 20mA/about 11bit, terminal 1: 0 to ±10V/12bit)
0.06Hz/60Hz (terminal 1: 0 to ±5V/11bit)
Digital input
0.01Hz
Frequency 
accuracy
Analog input
Within ±0.2% of the max. output frequency (25°C±10°C)
Digital input
Within 0.01% of the set output frequency
Voltage/frequency characteristics
Base frequency can be set from 0 to 400Hz  Constant torque/variable torque pattern or adjustable 5 points V/F can be selected
Starting torque
200% at 0.3Hz (0.4K to 3.7K), 150% at 0.3Hz (5.5K or higher) (under Real sensorless vector control or vector control 
Torque boost
Manual torque boost
Acceleration/deceleration time 
setting
0 to 3600s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/deceleration mode, backlash 
measures acceleration/deceleration mode are available.
DC injection brake
Operation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 30%) can be changed
Stall prevention operation level
Operation current level can be set (0 to 220% adjustable), whether to use the function or not can be selected
Torque limit level
Torque limit value can be set (0 to 400% variable)
Operation specifications
Frequency 
setting 
signal
Analog input
• Terminal 2, 4: 0 to 10V, 0 to 5V, 4 to 20mA (0 to 20mA) can be selected• Terminal 1: -10 to +10V, -5 to +5V can be selected
Digital input
Input using the setting dial of the operation panel or parameter unit
Four-digit BCD or 16-bit binary (when used with option FR-A7AX)
Start signal
Forward and reverse rotation or start signal automatic self-holding input (3-wire input) can be selected.
Input signals (twelve terminals)
The following signals can be assigned to Pr. 178 to Pr. 189 (input terminal function selection): multi speed selection, remote setting, stop-
on-contact, second function selection, third function selection, terminal 4 input selection, JOG operation selection, selection of 
automatic restart after instantaneous power failure, flying start, external thermal relay input, inverter run enable signal (FR-HC/FR-CV 
connection), FR-HC connection (instantaneous power failure detection), PU operation/external inter lock signal, external DC injection 
brake operation start, PID control enable terminal, brake opening completion signal, PU operation/External operation switchover, load 
pattern selection forward rotation reverse rotation boost, V/F switching, load torque high-speed frequency, S-pattern acceleration/
deceleration C switchover, pre-excitation, output stop, start self-holding selection, control mode changing, torque limit selection, start-
time tuning start external input, torque bias selection 1, 2
,  P/PI control switchover, forward rotation command, reverse rotation 
command, inverter reset,  PTC thermistor input, PID forward reverse operation switchover, PU-NET operation switchover, NET-
External operation switchover, command source switchover, simple position pulse train sign
, simple position droop pulse clear
DC feeding operation permission, DC feeding cancel, magnetic flux decay output shutoff, proximity do
, 0V calibration request 
.
Pulse train input
100kpps
Operational functions
Maximum/minimum frequency setting, frequency jump operation, external thermal relay input selection, polarity reversible operation, 
automatic restart after instantaneous power failure operation, electronic bypass operation, forward/reverse rotation prevention, 
remote setting, brake sequence, second function, third function, multi-speed operation, original operation continuation at 
instantaneous power failure, stop-on-contact control, load torque high speed frequency control, droop control, regeneration 
avoidance, slip compensation, operation mode selection, offline auto tuning function, online auto tuning function, PID control, 
computer link operation (RS-485), motor end orientation 
, machine end orientation 
, pre-excitation, notch filter, machine analyzer 
, easy gain tuning, speed feed forward, and torque bias 
Output signals
Open collector output 
(5  terminals)
Relay output (2 terminals)
The following signals can be assigned to Pr. 190 to Pr. 196 (output terminal function selection): inverter running, inverter running/start 
command on, up-to-frequency, instantaneous power failure/undervoltage, overload warning, output frequency (speed) detection, 
second output frequency (speed) detection, third output frequency (speed) detection, regenerative brake pre-alarm, electronic 
thermal relay function pre-alarm, PU operation mode, inverter operation ready, output current detection, zero current detection, PID 
lower limit, PID upper limit, PID forward rotation reverse rotation output, electronic bypass MC1, electronic bypass MC2, electronic 
bypass MC3, orientation complete 
, orientation fault 
, brake opening request, fan fault output, heatsink overheat pre-alarm, 
deceleration at an instantaneous power failure, PID control activated, motor temperature detection 
, during retry, PID output 
interruption, during 0V calibration 
, position control preparation ready 
*1
DC feeding, life alarm, fault output 1, 2, 3 (power-off 
signal), power savings average value update timing, current average monitor, maintenance timer alarm, remote output, forward 
rotation output 
, low speed output, torque detection, regenerative status output 
, start-time tuning 
completion, in-position completion 
, alarm output and fault output. Alarm code of the inverter can be output (4 bit) from the open 
collector.
Operating status
When used with the FR-
A7AY, FR-A7AR (option)
In addition to above, the following signal can be assigned to Pr.313 to Pr. 319 (extension output terminal function selection): control circuit 
capacitor life, main circuit capacitor life, cooling fan life, inrush current limit circuit life. (only positive logic can be set for extension 
terminals of the FR-A7AR)
Pulse train output
50kpps
For meter
Pulse train output
(Max. 2.4kHz: one terminal)
Analog output
(Max. 10VDC: one terminal)
The following signals can be assigned to Pr. 54 FM terminal function selection (pulse train output) and Pr. 158 AM terminal function selection 
(analog output): output frequency, motor current (steady or peak value), output voltage, frequency setting, operation speed, motor 
torque, converter output voltage (steady or peak value), electronic thermal relay function load factor, input power, output power, load 
meter, motor excitation current, reference voltage output, motor load factor,  motor temperature 
, power saving effect, regenerative 
brake dutyPID set point, PID measured value, motor output, torque command, torque current command, and torque monitor.
Indication
Operation 
panel 
(FR-DU07)
Parameter 
unit (FR-
PU07)
Operating status
The following operating status can be displayed: Output frequency, motor current (steady or peak value), output voltage, frequency 
setting, running speed, motor torque, overload, converter output voltage (steady or peak value), electronic thermal relay function 
load factor, input power, output power, load meter, motor excitation current, position pulse 
, cumulative energization time, 
orientation status 
, actual operation time, motor load factor, cumulative power, energy saving effect, cumulative saving power, 
regenerative brake duty, PID set point, PID measured value, PID deviation, inverter I/O terminal monitor, input terminal option 
, torque command, torque current 
command, feed back pulse 
, motor output, SSCNET III communication status 
, motor temperature 
Fault record
Fault definition is displayed when a fault occurs, the output voltage/current/frequency/cumulative energization time right before the 
fault occurs and past 8 fault records are stored.
Interactive guidance
Function (help) for operation guide 
Protective/ 
warning 
function
Protective function
Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage during 
acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection thermal operation, motor 
protection thermal operation, heatsink overheat, instantaneous power failure occurrence, undervoltage, input phase loss 
, motor 
overload, output side earth (ground) fault overcurrent, output short circuit, main circuit element overheat, output phase loss, external 
thermal relay operatio
, PTC thermistor operation
, option fault, parameter error, PU disconnection, retry count excess 
CPU fault, operation panel power supply short circuit, 24VDC power output short circuit, output current detection value excess 
inrush current limit circuit fault, communication fault (inverter), USB fault, opposite rotation deceleration fault
, analog input fault, 
brake transistor alarm, speed deviation large
, position error large
, encoder phase error
Warning function
Fan fault, overcurrent stall prevention, overvoltage stall prevention, regenerative brake pre-alarm 
, electronic thermal relay 
function pre-alarm, PU stop, maintenance timer alarm
, parameter write error, copy operation error, operation panel lock, 
password locked,  parameter copy alarm, speed limit indication
Environment
Surrounding air temperature
-10°C to +50°C (non-freezing) 
Ambient humidity
90%RH maximum (non-condensing)
Storage temperature
-20°C to +65°C
Atmosphere
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
Altitude/vibration
Maximum 1000m above sea level for standard operation. 5.9m/s
2
 or less 
 at 10 to 55Hz (directions of X, Y, Z axes) 
*1 Available only when the option (FR-A7AP/FR-A7AL) is mounted.
*2 Available only when the option (FR-A7AL) is mounted.
*3 Available only when the option (FR-A7NS) is mounted.
*4 Available only when the option (FR-A7AZ) is mounted and SF-
V5RU……………T/A is used.
*5 Available only when the option (FR-A7AD) is mounted.
*6 Can be displayed only on the operation panel (FR-DU07).
*7 Can be displayed only on the parameter unit (FR-PU07).
*8 Temperature applicable for a short period in transit, etc.
*9 2.9m/s
2
 or less for the 160K or higher.
*10 This protective function is not available in the initial status.