Wiring
2
2.3 Wiring
2.3.1
Terminal connection diagram
NOTE
y
To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also
separate the main circuit wire of the input side and the output side.
y
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
y
The output of the single-phase power input model is three-phase 200V.
Earth 
(Ground)
Motor
IM
Earth (Ground)
Three-phase 
AC power 
supply
MCCB
MC
R/L1
P1
P/+
PR N/-
S/L2
T/L3
U
V
W
Earth
(Ground)
*7  Brake resistor (FR-ABR, MRS type, MYS 
type) 
Install a thermal relay to prevent an 
overheat and burnout of the brake resistor. 
Always install a thermal relay when using 
a brake resistor whose capacity is 11K or 
higher. 
(The brake resistor can not be connected 
to the 0.1K and 0.2K.)
*8  It is not necessary when 
calibrating the indicator 
from the operation panel.
*9  Operation and parameter setting can be 
done from the parameter unit (FR-
PU07) and the enclosure surface 
operation panel (FR-PA07). 
(Use the option cable (FR-CB2     ).) 
RS-485 communication can be utilized 
from a personal computer and other 
devices.
Forward 
rotation start
Reverse 
rotation start
Middle 
speed
High 
speed
Low 
speed
Control input signals (No voltage input allowed)
24VDC power supply 
(Common for external power supply transistor)
Contact input common
STR
STF
RH
RM
RL
SD
PC
Relay output
Running
Open collector output
Open collector output common
Sink/source common
RUN
SE
A
B
C
Frequency setting signals (Analog)
2 0 to 5VDC
10(+5V)
2
3
1
4 4 to 20mADC
Frequency 
setting 
potentiometer
1/2W1k
Ω
Terminal 4 
input
(Current 
input)
(+)
(-)
5(Analog common)
*4  It is recommended to 
use 2W1k
Ω when the 
frequency setting signal 
is changed frequently. 
*4
*2 When using terminals PC-
SD as a 24VDC power 
supply, take care not to 
short across terminals 
PC and SD.
PU
connector
*
1.  DC reactor (FR-HEL) 
When connecting a DC reactor, remove the 
jumper across P1 and P/+. 
Single-phase 100V power input model is not 
compatible with DC reactor.
Control circuit terminal
Main circuit terminal
Sink logic
Jumper
*1
*7
*6
*2
*3
*5
The function of these 
terminals can be 
changed to the reset 
signal, etc. with the input 
terminal assignment   
(
Pr. 178 to Pr. 182)
.
Multi-speed selection
Terminal functions vary by 
Pr. 190 RUN terminal function 
selection
Terminal functions vary 
by 
Pr. 192 A,B,C terminal 
function selection
SINK
SOURCE
V
I
*5
0 to 5VDC
(0 to 10VDC)
0 to 10VDC
*5 Terminal input specifications can be changed by analog 
input specifications switchover (
Pr. 267). Set the 
voltage/current input switch in the "V" position to select 
voltage input (0 to 5V/0 to10V) and "I" (initial value) to 
select current input (4 to 20mA). 
To use terminal 4 (initial setting is current input), set "4" 
in any of 
Pr.178 to Pr.182 (input terminal function 
selection) to assign the function, and turn ON AU signal.
Voltage/current 
input switch
Main circuit
Control circuit
R
Relay output
(Fault output)
Brake unit
(Option)
FM
SD
Indicator
(Frequency meter, etc.)
+
-
Moving-coil type
1mA full-scale
Calibration resistor
*8
*9
*3 Terminal input specifications 
can be changed by analog 
input specifications 
switchover (
Pr. 73). 
Terminal 10 and terminal 2 
are used as PTC input 
terminal (
Pr. 561).
Safe stop input (Channel 1)
Safe stop input (Channel 2)
Safe stop input common
Safety stop signal
S1
S2
SC
SO
Shorting 
wire
Single-phase 
AC power 
supply
MCCB
MC
R/L1
S/L2
Single-phase power input
*6  Terminal P1 is not available for single-
phase 100V power input model.
*10  Common terminal of terminal SO is 
terminal SC. (Connected to terminal SD 
inside of the inverter.)
Safety monitor output *10
Terminal functions vary by 
Pr. 197 SO 
terminal function selection