not adjusted; however, it is available for 
temperature controlling. 
 
•  Setting Parameter: Press   for 6 seconds. Start 
parameter menu and PA (menu password) 
flashing. Enter the password by pressing
 or 
. Press
 again to choose the parameter. 
Press 
 or 
  then the parameter can be 
displayed and adjusted. After the adjustment, if 
no button has been pressed after 30 seconds, 
the system will restore the new parameter and 
go back to normal operations. 
•  Changing menu password (CPA): The CPA can 
be checked or changed only after the correct 
menu password has been entered. When it 
shows CPA, press 
 or 
 then the present 
password is displayed and can be changed to a 
new password. Press 
  to confirm the new 
password. (Please memorize the new password 
or you can never adjust other parameters.) 
•  The factory default resumption: Press   
button for 1 second and then press 
 button 
simultaneously for 6 seconds. The indicator will 
flash and then all parameters will be restored to 
back to the factory defaults. After 10 seconds, it 
will return to normal operation. 
Parameter details 
•  Temperature controlling: After turning on for 
the delay time (e4), the compressor starts 
operating when cold‐room temperature   (set 
temperature +hysteresis), and will off when 
cold‐room temperature   set temperature. To 
protect the compressor it can be re‐started, 
unless the time when the compressor stops 
every time is longer than the delay time (E4). 
•  Evaporator fan operating function: 
F5 is set “00”, parallel with compressor. 
F5 is set “01”, continuous running (except defrost). 
•  Electric heater defrost: evaporator sensor 
temperature < defrost termination temperature 
(F3), the heater will switch on and the defrost 
will start.  
After a defrost interval, it begins the automatic 
defrost function. e.g.: When the evaporator sensor 
temperature < defrost termination temperature 
(F3), the defrost LED will turn on, the compressor 
and fan will stop, and the heater will start. When 
the evaporator sensor temperature   defrost 
termination temperature or defrost duration (F1) 
ends, the heater and defrost will stop after the 
draining time (F6). The cold‐room temperature   
(set temperature + hysteresis), the compressor will 
starts and go back to refrigeration status.  
When the defrost interval time (f2) is set”00”, the 
function of the automatics defrost will be cancelled. 
Temperature displayed when defrost: If F4 is set 
“01”, it displays the temperature when the defrost 
starts. After defrost, It will continue to display this 
temp for 20 min and the defrost LED will begin 
flashing. It will then come back to normal 
temperature.  
•  Controlling the evaporator fan after defrost: 
Controlling by time: When F7 is set “00” after 
defrost, the compressor works for F8 and then 
the fan restarts. After defrost and the first 
working mode, the fan will follow the mode of 
F5. 
Controlling by temperature: When F7 is set “01” 
after defrost, when the evaporator temperature 
reaches F9, the fan restarts. After defrost and 
the first working mode, the fan will follow the 
mode of F5. 
•  Sensor failure work mode: If the cold‐room 
sensor is short circuited or overheated, “HH” 
will be displayed. If the cold‐room sensor is in 
an open circuit or the temperature is too low 
then “LL” is displayed. At that time the 
compressor will automatically go to a cycle of 
45 min on and 15 min off. When the evaporator 
sensor fails or surpasses the displayed range, 
the defrost termination will be just controlled 
by the defrost duration.