LEGEND
NOTES:
1. Certified in accordance with AHRI Standard 550/590 at standard
rating conditions.
2. Standard rating conditions are as follows:
Evaporator Conditions:
Leaving Water Temperature: 44 F (6.7 C)
Flow:
2.4 gpm per ton (0.043 L/s per kW)
Condenser Conditions:
Entering Water Temperature:85 F (29.4 C)
Flow: 
3.0 gpm per ton (0.054 L/s per kW)
Fouling Factor (Evaporator):
0.00010 hr x sq ft x F per Btuh (0.000018 m
2
 x K per W)
Fouling Factor (Condenser):
0.00025 hr x sq ft x F per Btuh (0.000044 m
2
 x K per W)
3. IPLV is a single number part-load efficiency value calculated from
the system full-load efficiency values and corrected for a typical
building air-conditioning application.
4. Contact Carrier for custom ratings.
5. Data shown for standard chiller with 2 pass, nozzle-in-head (NIH)
waterboxes.
30XW 
UNIT SIZE 
CAPACITY
INPUT 
POWER 
(kW)
EVAPORATOR 
FLOW
EVAPORATOR 
PRESSURE DROP
CONDENSER 
FLOW
CONDENSER 
PRESSURE DROP FULL LOAD 
EFFICIENCY 
(kW/Ton)
IPLV
(kW/Ton)
Tons
Output 
(kW)
gpm
L/s
Ft of 
Water
kPa
gpm
L/s
Ft of 
Water
kPa
325
322
1132.5
204.8
773
48.8
15.6
46.5
967
61.0
10.9
32.5
0.636
0.468
350
343
1206.3
215.7
824
52.0
17.5
52.2
1029
64.9
12.3
36.7
0.629
0.471
400
385
1354.0
242.8
924
58.3
21.5
64.1
1155
72.9
15.2
45.3
0.631
0.474
AHRI — Air Conditioning, Heating and Refrigeration Institute
IPLV — Integrated Part Load Value
Capacity ratings