2. LED Lights and Audible Alarm Safeties
At startup, a 5-second delay occurs while the control board conducts an internal timer 
check. A beep occurs when the control switch is moved to the "ICE" position. The red 
LED indicates proper control voltage and remains on unless a control voltage problem 
occurs. The green LEDs 1 through 4 energize and sequence from initial startup as listed 
in the table below. Note that the order of the LEDs from the outer edge of the control 
board is 1, 4, 3, 2. For details, see "II.B. Sequence of Operation."
Sequence Step
LED
Energized
Components
Time LEDs are On 
Min.
Max.
Avg.
1-Minute Fill Cycle
4
WV1
1 minute
Harvest Cycle
1, 4, 2
Comp, FMRs 
WV2, HGVs
2 minutes
20 minutes
3 to 5 minutes
Harvest Pump Timer
1, 3, 2
Comp, FMRs, 
PM, HGVs
0 seconds
50 seconds
harvest pump 
timer setting
Freeze Cycle
1 (and 4 for first 
1 min.)
Comp, FMRs, 
PM, LLVs 
(WV1 for first 1 
min.) 
5 minutes
freeze timer
setting
30 to 35 minutes
Pump-Out Cycle
1, 3, 2
Comp, FMRs,  
PM, HGVs, DV 
10 seconds
20 seconds
The built in safeties shut down the icemaker and have alarms as listed below.
No. of Beeps 
(every 3 sec.)
Type of Alarm
Notes
1
High Evaporator Temp.  
(temperature > 127°F (53°C))   
Check for harvest problem (stuck HGVs or relay), hot 
water entering icemaker, stuck HM, or shorted thermistor. 
2
Harvest Backup Timer 
(harvest > 20 min. for two cycles 
in a row)
Check for open thermistor, HGVs not opening, TXVs or 
LLVs leaking by, low charge, or inefficient Comp. 
3
Freeze Timer 
(freeze > specified setting for 
two cycles in a row)
Timer is factory set using S4 dip 
switch 9 & 10
Check for a F/S stuck closed (up), WV1 or WV2 leaking 
by, HGVs leaking by, PM not pumping, TXVs not 
feeding properly, LLVs not opening, low charge, HM not 
bypassing, or inefficient compressor. 
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6
Low Voltage 
(92Vac±5% or less)
Red LED will turn off if voltage protection operates.  
The control voltage safeties automatically reset when 
voltage is corrected.
7
High Voltage 
(147Vac±5% or more)
Legend: 
Comp–compressor; DV–drain valve; FMRs–fan motors-remote; 
  
F/S–float switch; HGVs–hot gas valves; HM–headmaster (C.P.R.); 
  
LLVs–liquid line valves; PM–pump motor; TXVs–thermostatic expansion 
valves; 
WV1–fill/refill water valve; WV2–harvest water valve