2.1.3 Power Requirements 
 
The electrical outlet should be located near the switch and be easily accessible. It must also be properly 
grounded. 
 
Make sure the power source adheres to the following guidelines: 
 
• 
Power: Auto Switching 90-260 VAC 
• 
Frequency range: 50/60 Hz 
 
2.1.4 Environmental Requirements 
 
The switch must be installed in a clean, dry, dust-free area with adequate air circulation to maintain the 
following environmental limits: 
 
• 
Operating Temperature: 0° to 40°C (32° to 104°F) 
• 
Relative Humidity: 10% to 90% non-condensing 
 
Avoid direct sunlight, heat sources, or areas with high levels
 
of electromagnetic interference. Failure to 
observe these limits may cause damage to the switch and void the warranty. 
 
2.1.5 Cooling and Airflow 
 
The IC35516 switches use internal fans for air-cooling. Do not restrict airflow by covering or obstructing air 
vents on the sides of the switch. 
 
2.2 Installation into an Equipment Rack 
 
Important! Before continuing, disconnect all cables from the switch. 
 
To mount the switch onto an equipment rack: 
 
1.  Place the switch on a flat, stable surface. 
2.  Locate a rack-mounting bracket (supplied) and place it over the 
mounting holes on one side of the switch. 
3.  Use the screws (supplied) to secure the bracket (with a Phillips 
screwdriver). 
4.  Repeat the two previous steps on the other side of the switch. 
5.  Place the switch in the equipment rack. 
6.  Secure the switch by securing its mounting brackets onto the equipment rack with the appropriate 
screws (supplied). 
 
Important! 
Make sure the switch is supported until all the mounting screws for each bracket are secured to 
the equipment rack. Failure to do so could cause the switch to fall, which may result in personal injury or 
damage to the switch. 
 
2.2.1 Equipment Rack Guidelines 
 
Use the following guidelines to ensure that the switch will fit safely within the equipment rack: 
 
• 
Size: 
IC35516-T: 17.1 x 10.1 x 1.6 inches (434 x 257 x 41 mm) 
IC35516-G: 17.5 x 14.0 x 2.6 inches (445 x 356 x 66 mm) 
• 
Ventilation: Ensure that the rack is installed in a room in which the temperature remains below 40° 
C (104° F). Be sure that no obstructions, such as other equipment or cables, block airflow to or 
from the vents of the switch 
• 
Clearance: In addition to providing clearance for ventilation, ensure that adequate clearance for 
servicing the switch from the front exists