Installation Drawings
11
Figure 7
Liebert NXL Maintenance Bypass Cabinet—250 and 300kVA outline drawing
NOTES:
1. All dimensions are in inches (mm).
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical while handling.
4. Top and bottom cable entry available through removable
    access plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Includes side panel. Side panels are removed between
    adjacent units which are bolted togethe r.
7. Control wiring and power wiring must be run in separate conduits.
8. Aluminum and copper-clad aluminum cables are not recommended.
9. All wiring is to be in accordance with national and local electrical codes.
10. Widths are without side panels. The width is 25.6" (650mm) with side panels.
11. The depth dimension includes the front door and rear panel.
CG
CG
KNOCK-OUT FOR
CONTROL WIRING
O  1"
3 PLCS
KNOCK-OUT FOR
CONTROL WIRING
O  1"
2 PLCS
CONDUIT
LANDING
AREA
CONDUIT
LANDING
AREA
24.2
(615)
33.5
(850)
76.8
(1951)
38.5
(979)
12.2
(309)
22.7
(578)
38.5
(979)
56.8
(1442)
21.1
(535)
31.3
(795)
24.8
(630)
24.0
(610)
4.9
(124)
TYP
3.9
(100)
TYP
21.9
(555)
16.1
(410)
TOP VIEW (DOOR OPEN)
BOTTOM VIEW (FOOTPRINT)
BOTTOM CONDUIT PLATES