Specifications
28
Table 11
Recommended conduit and cable sizes—Module Bypass Input
UPS
Rating
System Input Voltage (VAC)
Module Bypass Input
Nominal Selection
Alternate Selection
kVA kW Rectifier Bypass
Maint
Byp
Output
Top Cable Entry
Wire & Conduit
Ph, N, G,THW / FMC
Bottom Cable Entry
Wire & Conduit
Ph, N, G, THW / RNC
Top Cable Entry
Wire & Conduit
Ph, N, G, THW / FMC
Bottom Cable Entry
Wire & Conduit
Ph, N, G  THW / RNC
250 225
480
480
480
480
(2) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
(2) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
(3) 2C 3-#2/0AWG,
2-#2/0AWG, #1/0AWG
(3) 2.5C 3-#2/0AWG,
2-#2/0AWG, #1/0AWG
300 270
480
480
480
480
(2) 3.5C 3-350kcmil,
2-350kcmil, #1/0AWG
(2) 3.5C 3-350kcmil,
2-350kcmil, #1/0AWG
(3) 3C 3-#4/0AWG,
2-#4/0AWG, #1/0AWG
(3) 3C 3-#4/0AWG, 
2-#4/0AWG, #1/0AWG
400 360
480
480
480
480
(2) 4C 3-500kcmil,
2-500kcmil, #1/0AWG
(2) 4C 3-500kcmil,
2-500kcmil, #1/0AWG
(3) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
(3) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
500 450
480
480
480
480
(3) 3.5C 3-500kcmil,
2-250kcmil , #1/0AWG
(3) 4C 3-500kcmil,
2-250kcmil , #1/0AWG
(4) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
(3) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
Table 12
Recommended conduit and cable sizes—Module Output
UPS
Rating
System
Input Voltage (VAC)
Module Output
Nominal Selection
Alternate Selection
kVA kW Rectifier Bypass
Maint
Byp
Output
Top Cable Entry
Wire & Conduit
Ph, N, G  THW / FMC
Bottom Cable Entry
Wire & Conduit
Ph, N, G  THW / RNC
Top Cable Entry
Wire & Conduit
Ph, N, G  THW / FMC 
Bottom Cable Entry
Wire & Conduit
Ph, N, G  THW / RNC
250 225
480
480
480
480
(2) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
(2) 3C 3-250kcmil, 
2-250kcmil, #1/0AWG
(3) 2C 3-#2/0AWG,
2-#2/0AWG, #1/0AWG
(3) 2.5C 3-#2/0AWG,
2-#2/0AWG, #1/0AWG
300 270
480
480
480
480
(2) 3.5C 3-350kcmil,
2-350kcmil, #1/0AWG
(2) 3.5C 3-350kcmil,
2-350kcmil, #1/0AWG
(3) 3C 3-#4/0AWG,
2-#4/0AWG, #1/0AWG
(3) 3C 3-#4/0AWG,
2-#4/0AWG, #1/0AWG
400 360
480
480
480
480
(2) 4C 3-500kcmil,
2-500kcmil, #1/0AWG
(2) 4C 3-500kcmil,
2-500kcmil, #1/0AWG
(3) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
(3) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
500 450
480
480
480
480
(3) 3.5C 3-500kcmil,
2-250kcmil , #1/0AWG
(3) 4C 3-500kcmil,
2-250kcmil , #1/0AWG
(4) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
(4) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
Table 13
Recommended conduit and cable sizes—Load Output
UPS Rating
System Input Voltage (VAC)
Load Output
Nominal Selection
Alternate Selection
kVA
kW Rectifier Bypass
Maint
Byp Output
Top Cable Entry
Wire & Conduit
Ph, N, G  THW / FMC 
Bottom Cable Entry
Wire & Conduit
Ph, N, G  THW / FMC 
Top Cable Entry
Wire & Conduit
Ph, N, G  THW / FMC 
Bottom Cable Entry
Wire & Conduit
Ph, N, G  THW / FMC 
250
225
480
480
480
480
(2) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
(2) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
(3) 2C 3-#2/0AWG,
2-#2/0AWG, #1/0AWG
(3) 2.5C 3-#2/0AWG,
2-#2/0AWG, #1/0AWG
300
270
480
480
480
480
(2) 3.5C 3-350kcmil,
2-350kcmil, #1/0AWG
(2) 3.5C 3-350kcmil,
2-350kcmil, #1/0AWG
(3) 3C 3-#4/0AWG,
2-#4/0AWG, #1/0AWG
(3) 3C 3-#4/0AWG,
2-#4/0AWG, #1/0AWG
400
360
480
480
480
480
(2) 4C 3-500kcmil,
2-500kcmil, #1/0AWG
(2) 4C 3-500kcmil,
2-500kcmil, #1/0AWG
(3) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
(3) 3C 3-250kcmil,
2-250kcmil, #1/0AWG
500
450
480
480
480
480
(3) 3.5C 3-500kcmil,
2-250kcmil , #1/0AWG
(3) 4C 3-500kcmil,
2-250kcmil , #1/0AWG
(4) 3C 3-250kcmil, 
2-#4/0AWG, #1/0AWG
(4) 3C 3-250kcmil,
2-#4/0AWG, #1/0AWG
Table 14
Recommended conduit and cable sizes—Load Bank Output
UPS Rating
System Input Voltage, VAC
Load Bank Output
kVA
kW
Rectifier
Bypass
Maint Byp
Output
Nominal Selection
Front Cable Entry
Wire-3W + GND
250
225
480
480
480
480
(1) 3-500kcmil, #1/0AWG
300
270
480
480
480
480
(2) 3-#4/0AWG, #1/0AWG
400
360
480
480
480
480
(2) 3-350kcmil, #1/0AWG
500
450
480
480
480
480
(2) 3-500kcmil, #1/0AWG