Specifications
29
Notes
See the Liebert NXL UPS installation manual, SL-25420, for UPS rectifier, UPS bypass and UPS out-
put sizes. The manual is available at the Liebert Web site: 
These are guidelines only and are superseded by local regulations and codes of practice where appli-
cable.
• Take special care when determining the size of the neutral cable, as current circulating on the 
neutral cable may be greater than nominal current in the case of non-linear loads. Refer to the 
values given in the Tables 7 and 8.
• The ground conductor should be sized according to the fault rating, cable lengths, type of protec-
tion, etc. The ground cable connecting the UPS to the main ground system must follow the most 
direct route possible.
• Consideration should be given to the use of smaller, paralleled cables for heavy currents, as a way 
to ease installation.
• In most installations, the load equipment is connected to a distribution network of individually 
protected busbars fed by the maintenance bypass cabinet output rather than being connected 
directly to the Maintenance bypass cabinet itself. Where this is the case, the maintenance bypass 
cabinet output cables can be rated to suit the individual distribution network demands rather 
than being fully load-rated.
• When laying the power cables, do not form coils to avoid increasing formation of electromagnetic 
interference.
Table 15
Recommended lug sizes
Cable Size
T&B Series 54000 
Two Hole
#8 AWG
54850BE
#6 AWG
256-30695-868
#4 AWG
256-30695-733
#2-3 AWG
54811BE
#1 AWG
54857BE
#1/0 AWG
256-30695-593
#2/0 AWG
54862BE
#3/0 AWG
54864BE
#4/0 AWG
54866BE
250kcmil
54868BE
300kcmil
54870BE
350kcmil
54872BE
400kcmil
54874BE
500kcmil
54876BE
600kcmil
54878BE
750kcmil
54880BE
Use the T&B crimping tools recommended for these types of lugs.