5 - 1 
5   DATA LINK PROCESSING TIME 
MELSEC-QnA 
 
 
 
 
 
 
 
 
  5
 
 
 
 
 
 
 
 
 
 
 
 
5. DATA LINK PROCESSING TIME 
5.1 Status of Each Station When an Error Has Occurred 
The status of each station when an error has occurred is shown in the table below. 
 
Master station 
Remote I/O station
Data link status 
Remote input (RX)
Remote 
output 
(RY) 
Remote 
register 
(RWw) 
Remote 
register  
(RWr) 
Input Output 
When the master station's programmable controller CPU is 
stopped  
(data link continue) 
Continue 
All "0" 
Continue
Continue Continue
All points 
OFF 
When the local station's programmable controller CPU is 
stopped  
(data link continue) 
All points off only 
in the receive area 
from the stopped 
local station  1 
Continue Continue
Continue Continue Continue
Clear
Clear 
Master 
station  Keep
Keep 
– –  Keep 
Clear
When data link is 
stopped in the entire 
system 
Input-data status 
setting of faulty 
station (SW4) 
Local 
station  Keep
 
– 
All points 
OFF 
Clear
Clear the receive 
area from the 
remote I/O station 
with a 
communication 
error. 
Master 
station 
Keep
Keep the receive 
area from the 
remote I/O station 
with a 
communication 
error. 
Continue Continue
Continue 
Clear
When a communication 
error (power off, etc.) 
occurred in a remote I/O 
station 
Local 
station  Keep
 
– 
All points 
OFF 
Clear
Clear the receive 
area from the 
remote device 
station with a 
communication 
error. 
Master 
station 
Keep
Keep the receive 
area from the 
remote device 
station with a 
communication 
error. 
Continue Continue
Keep the 
receive area 
from the 
remote device 
station with a 
communication 
error. 
Clear
When a communication 
error (power off, etc.) 
occurred in a remote 
device station 
Input-data status 
setting of faulty 
station (SW4) 
Local 
station  Keep
 
Continue Continue
Clear
Clear the receive 
area from the local 
station with a 
communication 
error. 
Master 
station 
Keep
Keep the receive 
area from the local 
station with a 
communication 
error. 
Continue Continue
Keep the 
receive area 
from the local 
station with a 
communication 
error. 
Clear
When a communication 
error (power off, etc.) 
occurred in a local 
station 
Input-data status 
setting of faulty 
station (SW4) 
Local 
station  Keep
 
Continue Continue
1 : Because Yn0 (refresh instruct) is turned OFF.