Справочник Пользователя для Mitsubishi Electronics AJ61QBT11

Скачать
Страница из 294
 
 
 
5 - 2 
5   DATA LINK PROCESSING TIME 
MELSEC-QnA 
 
Remote device station 
Local station/standby master station/ 
intelligent device station 
Data link status 
Remote 
input 
(RX) 
Remote 
output 
(RY) 
Remote 
register 
(RWw) 
Remote 
register 
(RWr) 
Remote 
input 
(RX) 
Remote  
output  
(RY) 
Remote 
register  
(RWw) 
Remote 
register 
(RWr) 
When the master station's 
programmable controller CPU is stopped 
(data link continue) 
Continue 
All points 
OFF 
Continue Continue
All points 
OFF 
Continue Continue 
Continue
When the local station's programmable 
controller CPU is stopped (data link 
continue) 
Continue Continue Continue Continue Continue
Treat the host 
transmission 
area as all 
"0" 1. 
All points off 
only in the 
receive area 
from stopped 
local station 
Continue Continue
Clear 
Master 
station Keep 
 
Clear Clear 
Clear the 
receive area 
from the other 
station. 
When data link 
is stopped in 
the entire 
system 
Input-
data 
status 
setting of 
faulty 
station 
(SW4) 
Local 
station
Keep 
– 
All points 
OFF 
– – 
Keep 
Keep the 
receive area 
from the other 
station. 
Keep the 
receive area 
from the other 
station. 
Keep 
Clear 
Master 
station Keep 
 
Clear 
Clear the 
receive area 
from the 
remote I/O 
station with a  
communication 
error. 
When a 
communication 
error (power 
off, etc.) 
occurred in a 
remote I/O 
station 
Local 
station
Keep 
Continue Continue Continue Continue
Continue
Keep the 
receive area 
from the 
remote I/O 
station with a  
communication 
error. 
Continue Continue
Clear 
Master 
station Keep 
 
Clear 
Clear the 
receive area 
from the 
remote device 
station with a 
communication 
error. 
When a 
communication 
error (power 
off, etc.) 
occurred in a 
remote device 
station 
Input-
data 
status 
setting of 
faulty 
station 
(SW4) 
Local 
station
Keep 
– – – – 
Continue
Keep the 
receive area 
from the 
remote device 
station with a 
communication 
error. 
Keep the 
receive area 
from the 
remote device 
station with a 
communication 
error. 
Continue
1 : Because Yn0 (refresh instruct) is turned OFF.