MELSEC-QnA 
13   TROUBLESHOOTING 
 
Table 13.1 Error code list (5/6) 
Detectability 
Error code 
(hexadecimal) 
Error details 
Cause of error occurrence (details) 
Corrective action 
Master station 
Local station 
B801
1  Access code setting error 
A non-existing access code/attribute was 
set. 
Set a correct access 
code/attribute. 
 
 
B802
2  Access code error 
An access code that does not exist was 
used. 
Use the correct access code. 
 
 
B803
1  Data points error 
The number of data points were out of 
range. 
Set the number of data points 
to within 1 to 960 bytes. 
 
 
B804
Attribute definition error 
Transient transmission 
unsupported station 
specification error 
The attribute definition was invalid. 
Alternatively, transient transmission was 
performed even though the target station 
does not support transient transmission. 
Review the attribute definition. 
Check the designation of the 
target station number, as well 
as the function version and 
software version of the target 
local station. 
 
 
B805
1  Data points error 
The number of data was out of range. 
Set the range to within 1 to 100 
when writing, and 1 to 160 
when reading. 
 
 
B807
1 Device 
No. 
error 
The start device No. is out of range. 
Or, the address was not a multiple of 16 
when the bit device was accessed. 
Correct the start device No.. 
Or, set the address to a multiple 
of 16 when accessing the bit 
device. 
 
 
B80D
2 Setting 
range 
error 
The specified combination (addresses 
and points) exceeded the valid 
processing range. 
Set so that the number of 
processing points does not 
exceed the device range . 
 
 
B814
File register capacity setting 
error 
The file register capacity was not 
specified. 
Specify the file register 
capacity. 
 
 
B815
2  Module mode setting error 
A transient transmission was executed 
when the target station was set to the I/O 
mode. 
Set to the intelli mode. 
 
 
B823 
Remote control mode error 
The mode setting of the remote control 
was incorrect. 
Check the mode specification. 
 
 
B901 E
2
PROM error 
When a parameter registration request 
(YnA) to E
2
PROM was executed, 
E
2
PROM was out of order or exceeded 
its write limit (10,000 times). 
Replace the module. 
 
 
B902 
Error in data link startup by 
E
2
PROM parameter 
Data link start request by E
2
PROM 
parameter (YnB) was executed even 
though the parameter was not registered 
in E
2
PROM. 
Register the parameter to 
E
2
PROM by a parameter entry 
request (YnA). 
 
 
B903
1  Transient request error 
A transient request was issued to a 
station that has not secured a 
communication buffer area. 
Secure a communication buffer 
area with a parameter. 
 
 
B904
Communication buffer size 
setting error 
The communication buffer size of the 
corresponding station was out of range 
when a dedicated instruction was 
executed. 
Set the communication buffer 
size of the corresponding 
station within the range. 
 
 
B905
1  Transient data length error 
When the dedicated instruction is 
executed, the transient data length is 
greater than the communication buffer 
size of the corresponding station. 
Make the communication buffer 
size of the corresponding 
station greater than the 
transient data length. 
 
 
B907
Execution disabled during data 
link 
E
2
PROM erasure request (YnD: ON) was 
executed during data link (SB006E: ON).
Execute a data link stop using 
SW0002. 
 
 
B912
3  No registration area 
The parameter registration request to 
E
2
PROM (YnA: ON) was executed in 
excess of a maximum of 127 registration 
times. 
Execute the E
2
PROM erasure 
request (YnD: ON), switch 
power off, or reset the CPU. 
 
 
B913
3 E
2
PROM fault 
The parameter registration request to 
E
2
PROM (YnA: ON) was executed but 
E
2
PROM is faulty. 
Change the module. 
 
 
BA19 Corresponding 
station 
error 
The corresponding station that is being 
tested stopped communication during 
line test 1. 
Check the cable and the 
corresponding station. 
 
 
BA1B All 
stations 
error 
All stations stopped communications 
during line test 1. 
Check the cables. 
 
 
1: Error code added to the function version B or later. 
2: Error code added to the software version J (manufactured in Jan., 1998) or later. 
3: Error code added to the software version E (manufactured in Aug., 2001) or later of the A1SJ61QBT11.