Справочник Пользователя для Mitsubishi Electronics AJ61QBT11

Скачать
Страница из 294
 
 
 
13 - 11 
MELSEC-QnA 
13   TROUBLESHOOTING 
Table 13.1 Error code list (6/6) 
Detectability 
Error code 
(hexadecimal) 
Error details 
Cause of error occurrence (details) 
Corrective action 
Master station 
Local station 
BBC1 
Mode setting error (switch) 
The mode setting switch is set outside 
the range. 
Set it within the range. 
 
 
BBC2 
Station number setting error 
(switch) 
The station number setting switch setting 
of the module is other than "0 to 64". 
Alternatively, the last station number is 
greater than 64. 
Check the station number and 
the number of occupied stations 
of the module. 
 
 
BBC3 
Transmission speed setting 
error (switch) 
Module's transmission speed setting 
switch is set out of the range of "0 to 4". 
Set it in the range of "0 to 4." 
 
 
BBC4 
Station type change error 
(station number) 
An attempt was made to change the 
master station (0) to the local station (1 to 
64), or the local station (1 to 64) to the  
master station (0) by executing a module 
reset (Yn4). 
Change by resetting the 
programmable controller CPU. 
 
 
BBC5 
Master station overlapping error 
Multiple master stations exist on the 
same line. 
Alternatively, line noise was detected at 
power on. 
Reduce the number of master 
stations on the same line to 
one. 
Alternatively, check the line 
status. 
 
 
BBC6 
Mode change error 
An attempt was made to change the 
mode from 0 or 2 to the test mode by 
executing a module reset (Yn4). 
Change by resetting the 
programmable controller CPU. 
 
 
BBC7 
Module error 
Module is defective. 
Replace the module. 
 
 
BD85 Hardware 
error 
detection 
A hardware error was detected. 
The possible cause is the 
hardware failure of the 
AJ61QBT11/A1SJ61QBT11, 
CPU module, base unit, or 
other modules. Please consult 
your local Mitsubishi 
representative. 
 
 
BFFE 
CPU monitoring timer time out  The CPU monitoring timer timed out. 
Check the operation of the 
target station. 
 
 
C000 to 
CFFF 
An error detected in an Ethernet interface module 
Take a corrective action, referring to the troubleshooting description in the Ethernet Interface Module User's Manual. 
D000 to 
DFFF 
An error detected in CC-Link IE Field Network 
Take a corrective action, referring to the troubleshooting description in the CC-Link IE Field Network User's Manual. 
E000 to 
EFFF 
An error detected in CC-Link IE Controller Network 
Take a corrective action, referring to the troubleshooting description in the CC-Link IE Controller Network Reference Manual. 
F000 to 
FFFF 
An error detected in a MELSECNET/H and MELSECNET/10 network system 
Take a corrective action, referring to the troubleshooting description in the MELSECNET/H or MELSECNET/10 Network System Reference 
Manual.