1 - 12 
1   OVERVIEW 
MELSEC-QnA 
 
1.3.4 Compound system communication 
The overview of compound system communication with remote I/O stations, remote 
device stations, and local stations is described below. 
Refer to Section 4.5 for details. 
 
Refresh instruction
1
Master station
Data link startup
2
Buffer memory
Remote input (RX)
Remote output (RY)
Remote register (RWw)
Remote register (RWr)
Refresh instruction
1
Local station
Buffer memory
Remote output (RY)
Remote input (RX)
Remote register (RWr)
Remote register (RWw)
Input
Remote input (RX)
3
3
3
Output
Remote output (RY)
4
4
4
Remote register (RWw)
5
5
5
Remote register (RWr)
6
6
6
Remote I/O station
Remote device station
 
 
1
 Turn on the refresh instruction. 
2
 Startup the data link. 
3
 By the link scan, data in the remote I/O station's and remote device station's remote 
input (RX) and local station's remote output (RY) is sent to the master station's 
remote input (RX) and local station's remote output (RY). 
4
 By the link scan, data in the master station's remote output (RY) is sent to the 
remote I/O station's and remote device station's remote output (RY) and local 
station's remote input (RX). 
5
 By the link scan, data in the master station's remote register (RWw) is sent to the 
remote device station's remote register (RWw) and local station's remote register 
(RWr). 
6
 By the link scan, data in the remote device station's remote register (RWr) and local 
station's remote register (RWw) is sent to the master station's remote register (RWr) 