1   OVERVIEW 
MELSEC-QnA 
 
1.4 Number of Occupied Stations and Station Number, Number of Modules and Number of 
Stations 
The relationship between number of occupied station and station number, and 
between number of modules and number of stations is described below. 
 
(1)   Number of occupied stations 
The number of occupied stations is fixed for each module (remote I/O station, 
remote device station, and local station). 
However, the number of occupied stations can be set (1 to 4 stations ) for local 
stations. 
 
Module 
Number of occupied stations 
Remote I/O station (16 points and 32 points module) 
1 station 
AJ65BT-64AD 2 
stations 
AJ65BT-64DAV 2 
stations 
AJ65BT-64DAI 2 
stations 
AJ65BT-D62 
AJ65BT-D62D (S1) 
4 stations 
Remote device station 
A852GOT 
2 or 4 stations 
Local station 
1 to 4 stations  (changed by switch)
AJ65BT-R2(N) 1 
station 
AJ65BT-G4 1 
station 
Intelligent device station 
AJ65BT-D75P2-S3 4 
stations 
 The AJ61QBT11 of hardware version F or later and the A1SJ61QBT11 of hardware version G or later are 
compatible with this setting. For other than the above, the setting is 1 or 4 stations only. 
 
(2)   Station number 
When the number of occupied station for all connected stations is set to "1 
station," the station number is set continuously from 1 (e.g. 1, 2, 3,... ). 
However, when a station which occupies more than 2 stations is connected, the 
setting must be performed considering the number of occupied stations. 
 
Station No.5 Station No.6 Station No.7 Station No.8 Station No.9
Station No.4
Station No.3
Station No.2
Station No.1
Master
station
Local station
(occupies 4
stations)
Station No.4
Local station
(occupies 1
station)
Station No.9
Remote station
(occupies 2 stations)
Station No.1
Remote station
(occupies 1 station)
Station No.3
Remote station
(occupies 1 station)
Station No.8
 
 
(3)   Number of modules and number of stations 
Number of modules is a physical module count. 
Number of stations is a number of occupied stations for each module as stated in 
(1). 
In the system configuration example in (2), the number of modules is 5 and 
number of stations is 9.