3 - 11 
3   SPECIFICATION 
MELSEC-QnA 
 
(4)   Data link status at other stations: Xn3 
Indicates data link status at other stations (remote/local stations). 
SB0080 represents the same meaning. For programming, use either Xn3 or 
SB0080. 
OFF  : all stations normal 
ON  : error station exists (An error station status is stored in SW0080 to 83.) 
 
(5)   Module reset acceptance complete: Xn4 
Indicates the acceptance status of reset request by the module reset request 
(Yn4). 
Reset cannot be performed when module error (Xn0 on). 
 
(a)  When module reset request (Yn4) is turned on, module ready (XnF) turns off 
and initialization is executed. 
When the initialization is completed normally, module ready (XnF) turns on. 
Module reset request (Yn4) is turned off by turning on the module reset 
acceptance complete (Xn4). 
To make a data link, set the data link startup request (Yn6/Yn8) again. 
 
(Normal startup after reset) 
Module ready (XnF) 
Initialization
Module reset acceptance  
complete (Xn4)
Module reset request 
(Yn4)