Appendix 3.3 Instructions
Appendix 3.3.1 Instructions not supported in the Universal model QCPU 
and replacing methods
The Universal model QCPU does not support instructions listed in the TableApp.24. and TableApp.25
Instructions need to be replaced using replacing methods described in the tables. (If no instruction in the 
list is used, replacement is not required.)
TableApp.25 Instructions not supported in the Universal model QCPU and replacing methods
Symbol
Instruction
Replacing method
Reference
IX
Index modification of entire 
ladder
Instructions can be replaced using a replacement program.
Appendix 3.3.3 (1)
IXEND
IXDEV
Modification value specification 
in index modification of entire 
ladder
Change the program so that the device offset values 
specified by the IXSET instruction are directly set to the 
index modification table using the MOV instruction.
Appendix 3.3.3 (2)
IXSET
PR
Print ASCII code instruction
• It is recommended to use GOT as an ASCII code display 
device. ASCII codes stored in devices are directly 
displayed as characters on GOT.
• Instructions can be replaced using a replacement 
program.
Appendix 3.3.3 (3)
PRC
Print comment instruction
• It is recommended to use GOT as an ASCII code display 
device.Device comments can be displayed on GOT.
• Comment data can be output to a display device in the 
replacement program of the PR instruction after reading 
data using the reading device comment data instruction 
(COMRD(P)).
CHKST
Specific format failure check 
instruction
Instructions can be replaced using a replacement program.
Appendix 3.3.3 (4)
CHK
CHKCIR
Format change instruction for 
CHK instruction
Failure detection ladder patterns can be changed in a 
replacement program.
CHKEND
PLOW
Program low-speed execution 
registration instruction
• Use the PSCAN instruction instead of this instruction 
when low-speed execution type programs are replaced 
with scan execution type programs.
• No instruction can be used if low-speed execution type 
programs are replaced with fixed scan execution type 
programs.
---
PCHK
Program execution status 
check instruction
Check a program execution status on the Program monitor 
list screen of GX Developer. For details, refer to Section 
6.13.1 
in this manual.
---
KEY
Numerical key input instruction
• It is recommended to use GOT as a numeral input device.
• Instructions can be replaced using a replacement 
program.
Appendix 3.3.3 (5)
PLOADP
Load program from memory 
card 
Store all programs to be executed in the program memory. 
The Universal model QCPU can neither add programs to 
the program memory nor change them with other programs 
during RUN. If the capacity of the program memory is not 
enough, store parameters, device comments, and initial 
device values in the program memory into the standard 
ROM or a memory card instead.
---
PUNLOADP
Unload program from memory 
card
PSWAPP
Load + Unload