8 - 13 
8   PROGRAMMING 
MELSEC-QnA 
 
Table 8.1 Link special relay list (continued) 
 
Availability  
(  : available,  
   : not available )
Online 
Number Name 
Description 
Master 
station 
Local 
station
Offline
SB0020 1 Module 
status 
Stores the status of communications between the master/local module 
and the CPU module. 
OFF : Normal 
ON : 
Error 
 
 
 
SB0030 2 
Communication instruction 
(1) acceptance 
Indicates the acceptance status of SEND/RECV/READ/WRITE/REQ 
instructions (when channel 1 is used).(Usable on AJ61QBT11 and 
A1SJ61QBT11) 
OFF  : Not accepted 
ON : 
Accepted 
 
 
 
SB0031 2 
Communication instruction 
(1) complete 
Indicates the complete status of SEND/RECV/READ/WRITE/REQ 
instructions (when channel 1 is used). (Usable on AJ61QBT11 and 
A1SJ61QBT11) 
OFF  : Not completed 
ON : 
Completed 
 
 
 
SB0032 2 
Communication instruction 
(2) acceptance 
Indicates the acceptance status of SEND/RECV/READ/WRITE/REQ 
instructions (when channel 2 is used). (Usable on AJ61QBT11 and 
A1SJ61QBT11) 
OFF  : Not accepted 
ON : 
Accepted 
 
 
 
SB0033 2 
Communication instruction 
(2) complete 
Indicates the complete status of SEND/RECV/READ/WRITE/REQ 
instructions (when channel 2 is used). (Usable on AJ61QBT11 and 
A1SJ61QBT11) 
OFF  : Not completed 
ON : 
Completed 
 
 
 
SB0040 
Data link restart 
acceptance 
Indicates data link restart specification acceptance status. 
OFF  : Not accepted 
ON  : Startup specification accepted 
 
 
 
SB0041 
Data link restart complete 
Indicates data link restart specification acceptance complete status. 
OFF  : Not complete 
ON  : Startup complete 
 
 
 
SB0042 1 
Master station switch data 
link start acceptance 
Indicates the acceptance status of data link start switch instruction from 
the standby master station to the master station (Usable on the standby 
master station). 
OFF  : Not accepted 
ON : 
Accepted 
 
 
 
SB0043 1 
Master station switch data 
link start complete 
Indicates the acceptance status of data link start switch instruction from 
the standby master station to the master station (Usable on the standby 
master station). 
OFF  : Not Instruction 
ON : 
Completed 
 
 
 
SB0044 
Data link stop acceptance 
Indicates data link stop specification acceptance status. 
OFF  : Not accepted 
ON  : Stop specification accepted 
 
 
 
SB0045 Data 
link 
stop complete 
Indicates data link stop specification acceptance complete status. 
OFF  : Not complete 
ON  : Stop complete 
 
 
 
SB0048 1 
Temporary error invalid 
station acceptance 
Indicates the acceptance status of the temporary error invalid station 
request instruction. 
OFF  : Not accepted 
ON : 
Accepted 
 
 
 
SB0049 1 
Temporary error invalid 
station complete status 
Indicates the acceptance complete status of the temporary error invalid 
station request instruction. 
OFF  : Not executed 
ON  : Temporary error invalid station confirmed 
 
 
 
SB004A 1 
Temporary error invalid 
station cancelling 
acceptance status 
Indicates the acceptance status of the temporary error invalid station 
cancelling request instruction. 
OFF  : Not executed 
ON  : Instruction accepted 
 
 
 
SB004B 1 
Temporary error invalid 
station cancelling 
complete status 
Indicates the acceptance complete status of the temporary error invalid 
station cancelling request instruction. 
OFF  : Not executed 
ON  : Temporary error invalid station cancelling complete 
 
 
 
1: Link special relay added to the function version B or later 
2: Link special relay added to the software version J or later