8 - 14 
8   PROGRAMMING 
MELSEC-QnA 
 
Table 8.1 Link special relay list (continued) 
 
Availability  
(  : available,  
   : not available ) 
Online 
Number Name 
Description 
Master 
station 
Local 
station
Offline
SB004C 1 
Line test acceptance 
status 
Indicates the line test request acceptance status. 
OFF  : Not executed 
ON : 
Specification 
accepted 
 
 
 
SB004D 1  Line test complete status 
Indicates the line test complete status. 
OFF  : Not completed 
ON : 
Test 
complete 
 
 
 
SB004E 1 
Parameter setting test 
acceptance status 
Indicates the parameter setting test request acceptance status. 
OFF  : Not accepted 
ON : 
Specification 
accepted 
 
 
 
SB004F 1 
Parameter setting test 
complete status 
Indicates the parameter setting test complete status. 
OFF  : Not completed 
ON : 
Test 
complete 
 
 
 
SB0050 
Offline test status 
Indicates the offline-test execution status. 
OFF  : Not executed 
ON  : In progress 
 
 
 
SB0060 Mode 
Indicates the module's mode setting switch setting status. 
OFF : Online (0) 
ON  : Other than online (0) 
 
 
 
SB0061 Station 
type 
Indicates the setting status of the module station number setting 
switch. 
OFF  : Master station (station number 0) 
ON  : Local station (station numbers 1 to 64) 
 
 
 
SB0062 1 
Standby master station 
setting 
Indicates the setting status of the standby master station. 
OFF  : Not set 
ON : 
Set 
 
 
 
SB0065 
Input data status of a data 
link error station 
Indicates the setting status of the module's condition setting switch 
(DIP switch) SW4. 
OFF : Clear 
ON : 
Keep 
 
 
 
Indicates the setting of the module's condition setting switch (DIP 
switch) SW5, SW6. 
SB0066 
 
Number of 
occupied stations 
SB0066 (SW5) 
SB0067 (SW6) 
 
 1 
station 
OFF 
OFF   
 2 
stations 
OFF 
ON 
 
 3 
stations 
ON 
ON 
 
SB0067 2 
 4 
stations 
ON 
OFF   
Number of occupied 
stations 
 
 
 
SB0069 Module 
mode 
Indicates the setting status of the module's condition setting switch 
(DIP switch) SW8. (Usable on AJ61BT11 and A1SJ61BT11) 
OFF  : Intelligent mode 
ON  : I/O mode 
 
 
 
SB006A 
Switch setting status 
Indicates the switch setting status. 
OFF : Normal 
ON  : Setting error exists (Store the error code in SW006A) 
 
 
 
SB006D 
Parameter setting status 
Indicates the parameter setting status. 
OFF : Normal 
ON  : Setting error exists (Store the error code in SW0068) 
 
 
 
SB006E 
Host station operation 
status 
Indicates the data link communication status with other stations. 
OFF  : In operation 
ON  : Not in operation 
 
 
 
SB0070 1 
Master station data link 
status 
Indicates data link status. 
OFF  : Data link for master station 
ON  : Data link for waiting master station 
 
 
 
SB0071 1 
Standby master station 
information 
Indicates whether there is standby master station or not. 
OFF  : Not present 
ON : 
Present 
 
 
 
SB0072 1  Scan mode setting 
Indicates the scan mode setting status. 
OFF : Asynchronous mode 
ON  : Synchronous mode 
 
 
 
1: Link special relay added to the function version B or later 
2: Link special relay added to the AJ61QBT11 of hardware version F or later and the A1SJ61QBT11 of hardware version G or later