13 - 7 
MELSEC-QnA 
13   TROUBLESHOOTING 
 
Table 13.1 Error code list (2/6) 
Detectability 
Error code 
(hexadecimal) 
Error details 
Cause of error occurrence (details) 
Corrective action 
Master station 
Local station 
The station types of the module are 
different from parameter settings. 
Example) 
B30A 
Loading/parameter  
compatibility error 
Connected 
module
Remote 
device
Intelligent 
device
Parameter 
setting
Remote I/O
Remote 
device
Remote I/O
 
Set the correct parameters
 
 
B30B
1  Loading/parameter  
compatibility error 
The contents of the installation status 
and network parameters do not match. 
Set the contents of the 
installation status and network 
parameters to match. 
 
 
B30C
1  Standby master station 
specification error 
Master station switching was instructed 
to a station other than the standby 
master station. 
Specify the station number that 
corresponds to the standby 
master station. 
 
 
B30D
1 Initial 
status 
Temporary error invalid station 
specification. Line test request, or data 
link stop/restart request, etc. was issued 
before starting the link. 
Issue the requests after the 
data link is started. 
 
 
B30E Unsupported 
error 
In the function started by SB/SW, an 
attempt was made to execute the 
function, which is supported by only the 
master station, at the local station. 
Execute the corresponding 
function from the master 
station. 
 
 
B381 
Station number switch setting 
error 
The station number switch was outside of 
the setting range. 
Set the station number switch 
within the setting range. 
 
 
B383 
Transmission speed setting 
switch setting error 
The transmission speed setting switch is 
set outside the range. 
Set the transmission speed 
setting switch to within the 
setting range. 
 
 
B384 
Station number setting error 
(parameter) 
The station number (including the 
number of occupied stations) of the 
station information parameters (address 
20
H
 to 5F
H
) was set to "other than 1
 H
 to 
40
H
." 
Set within the range of "1
H
 to 
40
H
". 
 
 
B385 
Total number of stations error 
(parameter) 
The total number of occupied stations set 
with the station information parameter 
(address 20
H
 to 5F
H
) exceeded 64. 
Set a parameter value of 64 or 
less. 
 
 
B386 
Number of occupied stations 
setting error (parameter) 
The number of all occupied stations in 
the station information parameter 
(address 20
H
 to 5F
H
) was set to "0". 
Set the occupied station 
number to a value between "1 
and 4". 
 
 
B387 
Delay time setting error 
(parameter) 
The delay time setting in the master 
station network parameters is out of the 
setting range. 
Set a value within the setting 
range. 
 
 
B388 
Station type setting error 
(parameter) 
The station type in the station information 
parameter (address 20
H
 to 5F
H
) was set 
to "other than 0 to 2". 
Set to a value between "0 and 
2". 
 
 
B38B 
Remote device station setting 
error (parameter) 
The number of remote device stations 
was set to "43 stations or more" with the 
station information parameter (address 
20
H
 to 5F
H
). 
Set the remote device station to 
"42 stations or less" with the 
station information parameter. 
 
 
B38C 
Intelligent device station setting 
error (parameter) 
The number of intelligent device stations 
(including local stations) was set to "27 
stations or more" with the station 
information parameter (address 20
H
 to 
5F
H
). 
Set the intelligent device station 
to "26 stations or less" with the 
station information parameter. 
 
 
B38E
Communication buffer 
assignment error (parameter) 
The total size of the communication 
buffers in the station information 
parameter (address 20
H
 to 5F
H
exceeded 4 k words. 
Set the total size of the 
communication buffers to 4 k 
words or less. 
 
 
B38F
Automatic update buffer 
assignment error (parameter) 
The total size of the automatic update 
buffer in the station information 
parameter (address 20
H
 to 5F
H
exceeded 4 k words. 
Set the total size of the 
automatic update buffer to 4 k 
words or less. 
 
 
B390 
Standby master station 
specification error (parameter) 
The standby master station parameter 
(address 4
H
) was set to a value other 
than "1 to 64". 
Specify the standby master 
station to a value within the 
range from "1 to 64". 
 
 
1: Error code added to the function version B or later.