13 - 8 
MELSEC-QnA 
13   TROUBLESHOOTING 
 
Table 13.1 Error code list (3/6) 
Detectability 
Error code 
(hexadecimal) 
Error details 
Cause of error occurrence (details) 
Corrective action 
Master station 
Local station 
B391 
Retry count setting error 
(parameter) 
The retry count parameter (address 2
H
was set to a value other than "1 to 7". 
Set a value within the range 
from "1 to 7". 
 
 
B392 
Operation when CPU is down 
specified error (parameter) 
The operation when the CPU is down 
specification parameter (address 6
H
) was 
set to a value other than "0 or 1". 
Set "0 or 1". 
 
 
B393 
Scan mode specification error 
(parameter) 
The scan mode parameter (address 7
H
was set to a value other than "0 or 1". 
Set "0 or 1". 
 
 
B394 
Number of automatic return 
stations setting error 
(parameter) 
The number of automatic return stations 
parameter (address 3
H
) was set to a 
value other than "1 to 10". 
Set a value within the range 
from "1 to 10". 
 
 
B396 
Station number overlap error 
(parameter) 
A duplicate station number was specified 
with the station information parameter 
(address 20
H
 to 5F
H
). 
Set so that station numbers are 
not duplicated. 
 
 
B397 
Station information setting error 
(parameter) 
The station information parameter 
(address 20
H
 to 5F
H
) setting does not 
meet the following condition: 
(16 
 A) + (54 
 B) + (88 
 C) < 2304
A: Number of remote I/O stations 
B: Number of remote device stations 
C: Number of intelligent device stations 
(including local stations) 
Set the parameter so that it 
meets the condition shown on 
left. 
 
 
B398 
Number of occupied stations 
setting error (parameter) 
The number of occupied stations in the 
station information parameter (address 
20
H
 to 5F
H
) was set to a value other than 
"1 to 4". 
Set a value within the range 
from "1 to 4". 
 
 
B399 
Number of connected modules 
setting error (parameter) 
The number of connected modules 
parameter (address 1
H
) was set to a 
value other than "1 to 64". 
Set a value within the range 
from "1 to 64". 
 
 
B39A
Standby master station 
specification error (loading 
status) 
The status setting switch of the station 
number different from that specified with 
the parameter is set in the standby 
master station. 
Confirm the parameter or status 
setting switch. 
 
 
B39B 
Reserved station setting error 
(parameter) 
The parameter's reserve station 
specification is set to all reserve stations. 
Check the parameter's reserve 
station specification. 
 
 
B39C
Standby master station setting 
error 
The station information of the station 
number specified as the standby master 
station has been set to other than the 
intelligent device station. 
Correct the station information 
of the station specified as the 
standby master station to be 
the intelligent device station. 
 
 
B401
1  Parameter change error 
Parameter change was executed during 
transient request. 
Change the parameter after all 
transient requests are 
completed or before any are 
requested. 
 
 
B404
1 Response 
error 
A response from the requested station 
was not returned within the watchdog 
time period. 
Set a longer watchdog time. If 
an error persists, check the 
requested module and cables. 
 
 
B405
Transient applicable station 
error 
A transient request was made to a 
remote I/O station or a remote device 
station. 
Set the corresponding station to 
a local station or an intelligent 
device station. 
 
 
B406
1  RY simultaneous ON error 
RY is turned ON before the response is 
complete, or a request is issued without 
turning RY off. 
After the response is complete, 
always turn RY off before 
sending a request. 
 
 
B407
Transient communication 
number unmatched error 
The request data number is different from 
the response data number. 
Check the line. 
 
 