2   SYSTEM CONFIGURATION 
MELSEC-QnA 
 
2.2.2 Precautions when configuring a system 
Design the system with the following considerations to prevent mis-input from the 
remote I/O module: 
 
(1)   During power on and power off 
Start the data link after turning on the power for the remote I/O module. 
Turn off power for the remote I/O module after stopping the data link. 
 
During stop
During  
operation
ON
OFF
 Master module
 (Data-link status)
Remote I/O module  
(Power supply status)
Data link start
Data link stop
 
 
(2)   During momentary power failure of the remote I/O module 
When momentary power failure occurs with the power (24VDC) supplied to the 
remote I/O module, mis-input may occur. 
 
(a)   Cause for mis-input due to a momentary power failure 
The remote I/O module hardware uses the power after internally converting 
the module power (24VDC) in to 5VDC. 
When momentary power failure occurs with the remote I/O module, the 
following condition occurs: 
(Time for the 5VDC in the internal remote I/O module to turn off) > (input 
module on   off response time) 
Therefore, mis-input is caused when a refresh is performed within the time 
indicated by 
1
) in the diagram below. 
 
Remote I/O module 
(Module power supply 
and input external-power  
supply) 
Remote I/O module  
(Internal 5VDC)
Input (Xn) 
Because the input external-power supply is turned off,
the input (Xn) turns off after the response time of input
module is turned off. 