Справочник Пользователя для Mitsubishi Electronics A1SJ61BT11

Скачать
Страница из 294
 
 
 
8 - 16 
8   PROGRAMMING 
MELSEC-QnA 
 
Table 8.1 Link special relay list (continued) 
 
Availability  
(  : available,  
   : not available ) 
Online 
Number Name 
Description 
Master 
station 
Local 
station
Offline
SB0094 1 
Transient transmission 
status 
Indicates the transient transmission error occurrence status 
(SW0094 to SW00897). 
OFF : No error 
ON : 
Error 
Depending on the refresh timing, this relay may be updated with the 
difference of one sequence scan from the update of Transient 
transmission error status (SW0094 to SW0097). 
 
 
 
SB0095 1 
Master station transient 
transmission status 
Indicates the transient transmission status of the master station. 
OFF : Normal 
ON : 
Error 
 
 
 
SB00A0 2 
RECV instruction (1) 
execution request flag 
Indicates the RECV instruction execution request status (when 
channel 1 is used). (Usable on AJ61QBT11 and A1SJ61QBT11) 
OFF  : No execution request 
ON  : Execution request 
 
 
 
SB00A1 2 
RECV instruction (2) 
execution request flag 
Indicates the RECV instruction execution request status (when 
channel 1 is used). (Usable on AJ61QBT11 and A1SJ61QBT11) 
OFF  : No execution request 
ON  : Execution request 
 
 
 
1: Link special relay added to the function version B or later 
2: Link special relay added to the software version J manufactured in Jan., 1998 or later