8   PROGRAMMING 
MELSEC-QnA 
 
8.4.2 Link special register (SW) 
SW0000 to SW003F are stored in the sequence program, and SW0040 to SW00FF 
are automatically stored. 
The value in the (   ) next to the number indicates the buffer memory address. 
When using a master/local module as a standby master station, refer to the respective 
columns under "Availability" in the table as explained below. 
• When a standby master station is operating as a master station: "Master station" 
column 
• When a standby master station is operating as a standby master station: "Local 
station" column 
 
Table 8.2 Link special register list 
 
Availability  
(  : available,  
   : not available )
Online 
Number Name 
Description 
Master 
station 
Local 
station
Offline
SW0003  
(603
H
Multiple temporary error 
invalid station specification 
Selects whether to specifies multiple temporary error invalid stations: 
00 
: Specifies multiple stations as indicated in SW0004 to 
SW0007. 
01 to 64  : Specifies a single station from 1 to 64. 
 Specifies the station number used as the temporary error invalid station. 
 
 
 
Specifies the temporary error invalid station. 
0  : Not specified as a temporary error invalid station. 
1  : Specified as a temporary error invalid station. 
SW0004  
(604
H
SW0005  
(605
H
SW0006  
(606
H
SW0007  
(607
H
Temporary error invalid 
station specification  1 
1
SW0004
b0
1 to 64 in the table indicates station numbers.
2
b1
3
b2
4
b3
to
to
13
b12
14
b13
15
b14
16
b15
17
SW0005
18
19
20
to
29
30
31
32
33
SW0006
34
35
36
to
45
46
47
48
49
SW0007
50
51
52
to
61
62
63
64
 
 
 
 
SW0008  
(608
H
Line test station setting 
Sets the station to perform line tests. 
: Entire system (performed for all stations) 
01 to 64  : Specified station Default value : 0 
 
 
 
SW0009  
(609
H
Watchdog time setting 
Sets the response monitoring time for transient transmission. 
Default value   : 5 (s) 
Setting range  : 0 to 360 (s) 
 When a value out of the range is set, the value will be set to 360 seconds. 
 
 
 
SW000A  
(60A
H
CPU watchdog time 
setting 
Sets the CPU watchdog time when an access to CPU is gained through 
the AJ65BT-G4 using the dedicated instructions. 
Default value  : 5 (s) 
Setting range  : 0 to 3600 (s) 
 If a value out of the range is set, the value will be set to 3600s. 
Note: Set on the CC-Link master station or local station connected to the 
applicable CPU. 
 
 
 
SW0020  
(620
H
Module status 
Stores the status of communications between the master/local module 
and the CPU module. 
0 : 
Normal 
Other than 0  : Stores error code (Refer to the manual for the CPU 
module used.) 
 
 
 
SW0041 
(641
H
Data link restart result 
Stores the execution results of the data link restart specification by 
SB0000. 
0 : 
Normal 
Other than 0  : Stores error code (Refer to Section 13.3.) 
 
 
 
SW0043  
(643
H
Master station switch data 
link start result 
Indicates the switch specification execution result and stores the 
execution results of the master station switch data link start specification 
by SB0001.(Usable on standby master station) 
0 : 
Normal 
Other than 0  : Stores error code (Refer to Section 13.3.) 
 
 
 
SW0045 
(645
H
Data link stop result 
Stores the execution results of the data link stop specification by SB0002. 
0 : 
Normal 
Other than 0  : Error code (Refer to Section 13.3.) 
 
 
 
  : Link special relay added to the function version B or later 
1 : Turns on only the bit for the head station number.