Справочник Пользователя для Mitsubishi Electronics A1SJ61BT11

Скачать
Страница из 294
 
 
 
13 - 4 
MELSEC-QnA 
13   TROUBLESHOOTING 
 
13.2 Troubleshooting When the "ERR" LED on the Master Station Is Flashing 
 
To the next page
The "ERR" LED on the  
master station is flashing
Are the  
parameter setting  
and loading system  
configuration  
compatible? 
Are the  
master station  
link special registers  
SW0080 to SW0083  
(other station data  
link status)  
on?
Y
N
Y
Y
Y
Check the modules whose  
SW0098 to SW009B are on.
Are the station  
number switches
set correctly?
Malfunction of the  
corresponding module
Malfunction of  
the master station
Master station
malfunction
Set the station number
switches correctly.
Reset the power supply/ 
press the reset switch.
Check the modules whose  
SW0080 to SW0083 are on.
Is the power
supply on?
Is the "POWER"
LED on?
Is the "RD" LED on?
Turn on the power supply.
Is the supplied  
voltage within the
specified range?
Set the supplied voltage  
within the specified range.
Is the  
communication cable
correctly installed? 
 1
Wire the communication
cable correctly.
To the next page
To the next page
Malfunction of the  
corresponding module
Malfunction of the  
corresponding module
Are the  
master station  
link special registers  
SW0098 to SW009B  
(station overlap  
status) on?
N
N
Y
Y
N
Y
N
Y
N
Y
N
N
N
Check the master side.
Check the slave station side