13 - 6 
MELSEC-QnA 
13   TROUBLESHOOTING 
 
13.3 Error Codes 
Table 13.1 lists the error codes that are stored in the link special registers (SW). 
When a standby master station is used, refer to the respective columns under 
"Delectability" in the table as explained below. 
x
 When a standby master station is operating as a master station: "Master station" 
column 
x
 When a standby master station is operating as a standby master station: "Local 
station" column 
 
Table 13.1 Error code list (1/6) 
Detectability 
Error code 
(hexadecimal) 
Error details 
Cause of error occurrence (details) 
Corrective action 
Master station  Local station 
4000 to 
4FFF 
An error detected in a programmable controller CPU 
Take a corrective action, referring to the troubleshooting description in the user’s manual for the CPU module used. 
7000 to 
7FFF 
An error detected in a serial communication module 
Take a corrective action, referring to the troubleshooting description in the Serial Communication Module User's Manual or other relevant 
manuals. 
B104 
Data link restart error 
Data link restart (SB0000) was executed 
for the station that was performing a data 
link. 
Execute Data link restart (SB0000) 
for the station that has stopped a 
data link with Data link stop 
(SB0002). 
 
 
B105 
Data link stop error 
Data link stop (SB0002) was executed 
for the station that had stopped a data 
link. 
Execute Data link stop (SB0002) for 
the station that is performing a data 
link. 
 
 
B110
1  Transient data can not be 
received 
A line error has occurred. 
Check the line. 
 
 
B111
1  Transient data receiving order 
error 
A line error has occurred. 
Check the line. 
 
 
B112
1  Transient data length error 
A line error has occurred. 
Check the line. 
 
 
B113
1  Transient data ID error 
A line error has occurred or an 
instantaneous power failure has occurred 
at the send station. 
Check the line, or check the supply 
power and power supply module of 
the send station. 
 
 
B115
1  Link error 
A line error has occurred. 
Check the line. 
 
 
B116
1  Packet error 
A line error has occurred. 
Check the line. 
 
 
B201
1  Corresponding station error 
during sending 
A data link error occurred at the 
corresponding station during transient 
transmission. 
Check the data link status of other 
stations, if a temporary error invalid 
station is set, or if the corresponding 
station is stopped. 
 
 
B205 
Transient target station error 
A transient request was issued to other 
than the intelligent device station. 
Check the target station. 
 
 
B301 
Processing request error during 
link stop 
Line test request was issued while the 
link was stopped. 
Perform a line test while the link is 
being established. 
 
 
B302 
Specified station number 
setting error 
The specified station number exceeded 
the highest communication station 
number during temporary error invalid 
request/temporary error invalid cancel 
request. 
Specify a station number that is no 
greater than the highest 
communication station number. 
 
 
B303 
Specified station number not 
set error 
The station number was not specified during 
temporary error invalid request/temporary 
error invalid cancel request. 
Set a specified station number. 
(SW0003, SW0004 to SW0007) 
 
 
B304 
Line test error station detected 
An error was detected in a remote 
station, intelligent device station or 
standby master station when a line test 
was performed. 
Check that the remote station, 
intelligent device station or standby 
master station is operational and 
that the cable is not disconnected. 
 
 
B306 
Specified station number 
setting error 
A station number other than the head 
station number was specified during 
temporary error invalid request/temporary 
error invalid cancel request. 
Specify a head station when 
temporary error invalid 
request/temporary error invalid 
cancel request is requested. 
 
 
B307 
All stations data link error 
All stations were in data link error status 
when one of the following requests was 
made: 
•  SB0000 (data link restart) 
•  SB0002 (data link stop) 
Request again after the data link 
becomes normal. 
 
 
B308 
Station number setting error 
(installation status) 
The station number of the slave station is 
outside of the range between "1 and 64".
Set the station number of the slave 
station within the range between "1 
and 64". 
 
 
B309 
Station number overlap error 
The station number of the connected 
module was duplicated (including 
number of occupied stations). 
However, this excludes the duplicate 
head station number. 
Check the module station number. 
 
 
1: Error code added to the function version B or later.