FX Series Programmable Controller
Diagnostic Devices 6
6-7
6.6
Interrupt Control Flags
(M8050 to M8059 and D8050 to D8059)  
For symbol key see page 6-1.
Diagnostic
Device
Operation
Diagnostic
Device
Operation
M8050 (
)
I00
 disable
When the EI (FNC 04) 
instruction is driven in the 
user program, all interrupts 
are enabled unless the spe-
cial M devices noted here 
are driven ON. In that case 
for each special M coil that is 
ON, the associated interrupt 
is disabled, i.e. will not oper-
ate.
Note 
 denotes all types of 
that interrupt
D8050 -D8059
Reserved
M8051 (
)
I10
 disable
M8052 (
)
I20
 disable
M8053 (
)
I30
 disable
The following assignments only refer to 
FX, FX
2C
 FX
2N(C)
 PLC’s
The following assignments only refer to 
FX
0
, FX
0S
 and FX
0N
 PLC’s
M8054 (
)
I40
 disable
When the EI (FNC 04) 
instruction is driven in the 
user program, all interrupts 
are enabled unless the spe-
cial M devices noted here 
are driven ON. In that case 
for each special M coil that is 
ON, the associated interrupt 
is disabled, i.e. will not oper-
ate.
Note 
 denotes all types of 
that interrupt
M8054
Reserved
M8055 (
)
I50
 disable
M8055
Reserved
M8056 (
)
I6
 disable
M8056 (
)
X0 pulse catch
When the leading edge of a 
pulse is received at an input 
from the range X0 to X3 the 
associated M device detailed 
here is set ON. By resetting 
the same device within the 
user program the next pulse 
occurrence will again set the 
M coil ON. Hence, fast input 
pulses are 'caught' and 
stored. This operation contin-
ues regardless of any EI 
(FNC04) and DI (FNC 5) 
instructions.
For FX, FX
2C
, FX
2N
 operation 
see page 6-12
M8057 (
)
I7
 disable
M8057 (
)
X1 pulse catch
M8058 (
)
I8
 disable
M8058 (
)
X2 pulse catch
M8059(
)
I010 to I060
disabled as a
single group
(FX
(2C)
, FX
2N
 
only)
M8059 (
)
X3 pulse catch
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)