Справочник Пользователя для Mitsubishi Electronics FX

Скачать
Страница из 382
FX Series Programmable Controllers
Assigning System Devices 9
9-2
9.2
Using The FX2-24EI With F
Series Special Function Blocks
The FX
2
-24EI allows an FX base unit to be directly connected to an one of the following F
series special function blocks:
a) The F-16NT/NP, a Melsec Net Mini interface
b) The F2-6A, a combine analog 4 input and 2 output unit
c) The F2-32RM, a programmable CAM sequencer
d) The F2-30GM, a pulse train positioning unit
One 24EI unit can control one F series special function unit.
The ‘24EI’ units are added to an FX system in the same manner as an additional discreet 
I/O module. Each 24EI occupies 16 input points and 8 output points, the diagram below 
illustrates this point. Experienced users may notice that the example shown in the 
diagram below would require too much power from the CPU unit (FX-48MR in this case) 
based on the I/O count.
This is not the case. The FX2-24EI is really a communications module. It does not 
directly drive any discreet I/O. For the sake of power calculations it can be assumed that 
it only occupies 8 standard I/O points. This means that the configuration shown in the 
diagram actually occupies 32 points (three FX2-24EI’s and one FX-8EX) of I/O for the 
sake of power consumption calculations BUT actually occupies 80 points of addressable 
I/O.
Connection Of Earth Points When Using F Series Special Function Blocks
When using the F series special function blocks the special function blocks earth 
terminal should be connected to the [SG] terminal of the FX CPU unit. However, when 
using the F-16NP/NT unit the [SG] terminal of the F-16NP/NT should on NO account be 
connected to the [SG] terminal of the FX. The function of these terminals are completely 
different and are hence NOT compatible.
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)
POWER
FX -24EI
2
POWER
FX -24EI
2
POWER
FX -24EI
2
POWER
FX-8EX
X30-47
Y30-37
X40-57
Y40-47
X50-57
Y50-57
X110-
Y117
Inputs X0-27
FX-48MR
Outputs Y0-27