FX Series Programmable Controllers
Assigning System Devices 9
9-4
9.2.2
Using the FX
2
-24EI With A F
2
-6A
The F
2
-6A’s operational address is based upon the position of the associated FX
2
-24EI within
the users FX system. However, the I/O channel numbers are not affected by this operational
address. The I/O channel will always remain as K000 to K001 and K010 to K013. The diagram
on the previous page shows how moving the position of the FX
address. The I/O channel will always remain as K000 to K001 and K010 to K013. The diagram
on the previous page shows how moving the position of the FX
2
-24EI used alters the
operational address but NOT the channel number used by the F
2
-6A, see EX. 1A to 1C.
For details on using the F
2
-6A see the units users manual. Please remember when reading the
manual, that it has been written for use on an F
2
system and hence all of the I/O addresses
stated are for such an F
2
setup.
F
2
-6A Channel identification:
•
Analog output channels are - K000 and K001 (2 points)
•
Analog input channels are - K010, K011, K012 and K013 (4 points)
Applicable FX Applied Instructions:
(Not applicable to FX
(Not applicable to FX
2C
Main Processing Units or FX units with CPU’s greater than version
3.06)
• FNC 91, ANRD - used to read the analog data in to the FX
•
FNC 92, ANWR - used to write the data from the FX to the F
2
-6A for output
9.2.3
Using the FX
2
-24EI With A F
2
-32RM
The F
2
-32RM’s operational address is based upon the position of the associated FX
2
-24EI
within the users FX system. However, the “32RM’s” I/O numbers are will always remain the
same, i.e not be affected by the FX’s operational address. The 32RM’s I/O numbers would
remain as Y0 to Y37, and Bank 0, 1. The diagram on the previous page shows how moving the
position of the FX
same, i.e not be affected by the FX’s operational address. The 32RM’s I/O numbers would
remain as Y0 to Y37, and Bank 0, 1. The diagram on the previous page shows how moving the
position of the FX
2
-24EI used, alters the operational address but NOT the I/O numbers used
by the F
2
-32RM, see EX. 1A to 1C.
For details on using the F
2
-32RM see the units users manual. Please remember when reading
the manual, that it has been written for use on an F
2
system and hence all of the I/O addresses
stated are for such an F
2
setup.
Applicable FX Applied Instructions:
(applicable to all FX and FX2C Main Processing Units)
(applicable to all FX and FX2C Main Processing Units)
•
FNC 93, RMST - used to output a start code from the FX to the F
2
-32RM
•
FNC 94, RMWR - used to disable outputs on the F
2
-32RM
•
FNC 95, RMRD - used to read the ON/OFF status of the F
2
-32RM
•
FNC 96, RMMN - used to monitor speed and current position of the F
2
-32RM
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)