SETTINGS AND PROCEDURES BEFORE 
OPERATION
5.1 Q Series Safety Relay Module
5.1.4 Mounting/removal
5
 - 8
1
O
V
ER
VI
E
W
2
S
YST
EM
 
CONF
IGURA
T
ION
3
S
P
E
C
IF
ICA
T
IONS
4
F
UNCT
IO
NS
5
S
E
T
T
INGS
 A
ND 
PR
O
C
E
DURES
 BEF
ORE 
OP
E
R
A
T
ION
6
T
R
O
U
BL
ESH
O
O
T
ING
AP
PENDI
X
(3) Installation precautions
(a) Install a base unit on a flat surface.
If the surface is not flat, the printed circuit board is distorted, resulting in 
malfunction of the modules mounted.
(b) If there is a vibration source, such as an electromagnetic contactor or no fuse 
breaker, separate the control panel or keep enough clearance from the vibration 
source to install the programmable controller.
In addition, keep the clearances shown below between the programmable 
controller and devices (such as contactors and relays) to avoid being affected by 
radiated noise or heat.
 • In front of the programmable controller: 100mm or more
 • On the right or left of the programmable controller: 50mm or more
(c) When installing a programmable controller to a control panel, do not mount any 
module in the rightmost slot of the base unit.
Before uninstalling, remove the module mounted in the rightmost slot of the base 
unit.
Figure 5.6 Clearance from other devices
50mm 
or more
50mm 
or more
Device (such as contactor and relay)
100mm or more