5.2 CC-Link Safety Relay Module
5.2.1 Start-up procedures
5
SETTINGS AND PROCEDURES BEFORE 
OPERATION
5.2
CC-Link Safety Relay Module
5.2.1
Start-up procedures
Figure 5.7 shows start-up procedures for the CC-Link safety relay module.
Figure 5.7 Start-up procedures (1/2)
 * 1: Refer to Section 5.3
Yes
No
Start
Install the modules to a control panel 
or machine.
Set the extension module station 
number and extension communication 
terminating resistor setting switch.
*1
Connect the main module and an 
extension module with a safety circuit 
part extension cable.
*1
Mount a master module, local 
module, and standby master module 
on the base unit.
Connect the main module with 
CC-Link dedicated cable and connect 
terminating resistor to both ends of 
the module.
Connect 
an extension module?
Connect the monitor part (EA, EB, EG, 
EP) with shielded cable.
Connect a safety part terminating 
connector to the last module.
Set start-up mode with start-up mode 
setting switch.
(To next page)