Справочник Пользователя для Mitsubishi Electronics #NAME?

Скачать
Страница из 96
5
 - 13
5.2 CC-Link Safety Relay Module
5.2.3 Part names and settings
5
SETTINGS AND PROCEDURES BEFORE 
OPERATION
 Table 5.2 Part names (2/2)
Number
Name
Description
1)
Indicator LED
Z
Indicates status of safety output Z.
ON:
OFF: 
Safety output is generated (both K0 and K1 are ON).
Safety output is not generated.
X0
Indicates status of safety input (X0, X1).
X1
ON: 
OFF: 
Safety output is generated.
Safety output is not generated.
K0
Indicates operating status of the internal safety relay K0 (coil status of K0).
ON:
Operating status of the internal safety relay K0 is ON.
OFF:  Operating status of the internal safety relay K0 is OFF.
K1
Indicates operating status of the internal safety relay K1 (coil status of K1).
ON:
Operating status of the internal safety relay K1 is ON.
OFF:  Operating status of the internal safety relay K1 is OFF.
2)
CC-Link part, extension communication part 
terminal block
DA, DB, DG: Data terminal for CC-Link cable
SLD: Shielding wire terminal of CC-Link cable
EA, EB, EG: Data terminal for extension communication
EP: Power supply terminal for extension module
3)
Module power supply part terminal block
+ 24V: Module power supply + 24V terminal
24G: Module power supply 24G terminal
4)
Safety input part terminal block
X0
X0: Safety input X0 input terminal
COM: Safety input X0 COM terminal
X1
X1: Safety input X1 input terminal
COM: Safety input X1 COM terminal
5)
Safety power supply, start-up 
part terminal block
XS
XS0, XS1: Start-up off check terminal
+ 24V: Safety power supply + 24V terminal
24G: Safety power supply 24G terminal
6)
Safety output part terminal block
Z00, Z01: Safety relay output terminal
Z10, Z11: Safety relay output terminal
Z20, Z21: Safety relay output terminal
7)
CC-Link transmission speed 
terminating resistor setting 
switch
1 to 4
A switch for setting transmission speed of the CC-Link system and if 
terminating resistor is attached to the CC-Link system or not
•Transmission speed setting (Switch number from 1 to 3)
Set the transmission speed within the range from 0 to 4.
•Setting if CC-Link terminating resistor is attached or not (Switch number 4)
Setting switch LT
ON: Terminating resistor is attached.
OFF: Terminating resistor is not attached.
8)
CC-Link station number setting 
switch
STATION No.
A switch for setting the station number of CC-Link system
•Set tens place of the station number with "  10" of "STATION No.".
•Set ones place of the station number with "  1" of "STATION No.".
Set a station number within the range from 1 to 64.
(Repeat use of a station number is not possible.)
9)
Start-up mode setting switch
A switch for setting start-up mode
"A" side: Auto mode
"M" side: Manual mode
10)
Safety part extension connector OUT
A connector for connecting an extension module
11)
Serial number display
A serial number same as the one shown on the rating plate
Setting
Setting switch status (B RATE)
Transmission 
speed
4
2
1
0
OFF
OFF
OFF
156kbps
1
OFF
OFF
ON
625kbps
2
OFF
ON
OFF
2.5Mbps
3
OFF
ON
ON
5Mbps
4
ON
OFF
OFF
10Mbps