Справочник Пользователя для Eaton Electrical SC200
Appendix
A
Glossary of Alarms
Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.
IPN 997-00012-41D December 2006
A-1
AC Fail
All rectifiers are reporting loss of AC power.
ACD Fan Fail
The AC Distribution cooling system or fan controller has failed.
Aux Temp High
The auxiliary temperature sensor is at a temperature above the high
temperature set point.
temperature set point.
Aux Temp Low
The auxiliary temperature sensor is at a temperature below the low
temperature set point.
temperature set point.
Aux Temp Sensor Fail
The auxiliary temperature sensor is incorrectly configured,
disconnected, not fitted or faulty.
disconnected, not fitted or faulty.
Batt Temp High
This alarm indicates either thermal runaway of the batteries or that
the batteries are operating at a temperature that may cause reduced
battery life.
the batteries are operating at a temperature that may cause reduced
battery life.
Batt Temp Low
This alarm indicates a risk to the battery standby power system.
Note that lower temperatures reduce the battery capacity.
Note that lower temperatures reduce the battery capacity.
Battery Fuse Fail
(displayed as Batt Fuse Fail)
The batteries may no longer be powering the load.
Battery Test Active
A Battery Test is active.
Battery Test Fail
The batteries do not have the required capacity or are not operating
in a fully charged state.
in a fully charged state.
Equalize Active
An Equalize process is active.
Fast Charge Active
A Fast Charge process is active.
High Float
The float voltage is above its normal range.
High Load
The bus voltage is higher than the range that is safe for a reliable
load.
load.
In Discharge
The batteries are discharging.
Load Fuse Fail
The Load Fuse Fail digital input to the SM45 is active.
Low Float
The float voltage is below its normal range.
Low Load
The bus voltage is below its normal range.