ITW Dynatec c. 1999 
 
Page 3 - 3 
TPC-2 TIMER Manual #50-05 
 
Revised 1/99 
System Status Lights 
There are four LED’s in the top right corner of the Display Panel that provide an 
indication of the current system status. These lights are described in further detail below: 
Drive 1 & Drive 2 
These LED’s provide an indication of the current Drive Output activity. The LED’s will 
be in one of the following states: 
 
STATUS LIGHT 
MEANING 
No Illumination: 
There is no Drive Output activity 
GREEN: 
The Drive Output is functioning properly and is currently energized 
RED: 
There is an electrical short or other fault in the Drive Output, Output Cable or Glue Valve 
An electrical short circuit most likely exists if a Drive Status Light is red. Completely 
inspect the Output Cables and Glue Valve for the cause. Turn OFF, then turn back ON 
the TPC-2 Control Unit to clear the fault condition once the cause of the fault has been 
located. See the TROUBLESHOOTING section of this manual for more information in 
the event of a Drive Output fault. 
A.T.S. 
The Automatic Tip Sealer output is provided for use with cold glue systems that may 
employ tip sealing devices to prevent the glue from drying in the applicator nozzle during 
periods of glue system inactivity. This LED provides an indication of the current A.T.S. 
Drive Output activity. The LED will be in one of the following states: 
 
 
STATUS LIGHT 
MEANING 
No Illumination: 
There is no A.T.S. Output activity. The A.T.S. Output automatically deactivates when the 
TPC-2 does not receive a Trigger Input for 2.5 seconds. 
GREEN: 
The A.T.S. Output is functioning properly and is currently energized. The A.T.S. Output 
should activate immediately upon receipt of a Trigger Input. 
RED: 
There is an electrical short or other fault in the A.T.S. Output circuitry, Output Cable or 
Glue Valve 
An electrical short circuit most likely exists if the A.T.S. Status Light is red. Completely 
inspect the Output Cable and Tip Sealing Device for the cause. Turn OFF, then turn back 
ON the TPC-2 Control Unit to clear the fault condition once the cause of the fault has 
been located. See the TROUBLESHOOTING section of this manual for more 
information in the event of an A.T.S. Drive Output fault.