TROUBLESHOOTING 
NOTE:  Before any assumptions are made regarding an apparent fault, first check the 
input supply voltage. The voltage should be within ± 10% of the rated supply (i.e. 
115VAC or 230VAC). Any variation from these parameters can result in controller 
malfunction. 
Controller Glues Every Other Sheet 
Is the Trigger Device (photo eye) too far ahead of the Glue Applicator? The controller 
could still be performing a gluing cycle on “Product #1” when “Product #2” is detected if 
the physical distance between the Trigger Device and Glue Applicator is greater than the 
gap between sheets. The TPC-2 Control Unit will not respond to a Trigger Signal until 
the previous gluing cycle has been completed. 
Glue Line Moves or Changes Length 
The TPC-2 Control Unit has only the Trigger Device input that it can use to accurately 
apply a glue pattern. Great care should be taken to ensure that the Trigger Device 
sensitivity and vertical positioning are correctly adjusted as per the Trigger Device’s User 
Manual. Things to check include: 
1. Does the sheet change speed after it has been detected by the Trigger Device? 
This could occur due to drive device slippage, detecting the product during the transition 
from control by a “feeding device” to control by the “drive device” or there may be some 
kind of obstruction in the feed path, such as dried glue. Tightening or replacement of 
worn drive devices my resolve this problem. Moving the Glue Applicator and Trigger 
Device to a different point on the machine may also be a solution. 
2. Is the speed of the parent machine constant? 
It is essential that once the TPC-2 Control Unit has been programmed that the speed of 
the machine is not changed. Any machine speed change will require reprogramming the 
TPC-2 to again achieve proper glue pattern positioning on the product. 
Glue Applicators Will Not Activate 
1. Is the Trigger Device activated for a shorter duration than the programmed DELAY for 
EVENT1? 
The TPC-2 avoids “false triggers” by requiring that the Trigger Device be activated for at 
least the duration of the DELAY programmed into EVENT1 of each CHANNEL. 
2. Is the red LED above the RUN/STOP button illuminated?